2018-08-27 08:37:46PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ARCHITECTURAL PLANS HAVE SEVERAL REFERENCES TO
 THE FBC FIFTH EDITION (2014). THE FBC SIXTH EDITION
 (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL NEW
 PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE REQUIRED
 TO COMPLY WITH AND REFERENCE THE FBC SIXTH EDITION
 (2017). UPDATE THE CODE REFERENCES ON THE PLANS. FS
 CHAPTER 553
  
 2) THE VALUATION OF $75,000.00 FOR THIS PROJECT APPEARS
 TO BE LOW. SUBMIT A DETAILED LINE ITEM COST ESTIMATE
 FOR THE ENTIRE SCOPE OF WORK, INCLUDING DESIGN FEES,
 OVERHEAD AND PROFIT. FBC 109.3 BUILDING PERMIT
 VALUATION. FOR PERMITTING PURPOSES, VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD AND PROFIT;
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET
 BY THE BUILDING OFFICIAL.
  
 3) THE CITY OF WEST PALM BEACH'S FLOOD ORDINANCE
 REQUIRES ALL PROJECTS THAT ARE CONSIDERED SUBSTANTIAL
 IMPROVEMENTS MEET THE CURRENT RULES FOR CONSTRUCTION IN
 A SPECIAL FLOOD HAZARD AREA. SUBSTANTIAL IMPROVEMENT
 MEANS ANY COMBINATION OF REPAIR, RECONSTRUCTION,
 REHABILITATION, ALTERATION, ADDITION, OR OTHER
 IMPROVEMENT OF A BUILDING OR STRUCTURE, FOR WHICH THE
 CUMULATIVE COST IN ANY FIVE YEAR PERIOD EQUALS OR
 EXCEEDS 50 PERCENT OF THE MARKET VALUE OF THE BUILDING
 OR STRUCTURE AT THE END OF THE FIVE YEAR PERIOD AND
 BEFORE THE IMPROVEMENT OR REPAIR IS STARTED. IF THE
 STRUCTURE HAS INCURRED "SUBSTANTIAL DAMAGE," ANY
 REPAIRS ARE CONSIDERED SUBSTANTIAL IMPROVEMENT
 REGARDLESS OF THE ACTUAL REPAIR WORK PERFORMED.
 ACCORDING TO THE FLOOD INSURANCE RATE MAP WHICH WAS
 ADOPTED ON OCTOBER 5, 2017 BY THE CITY OF WEST PALM
 BEACH AND IS APPLICABLE TO THIS PROJECT, THE STRUCTURE
 IS LOCATED IN AN AE FLOOD ZONE WHICH IS A SPECIAL FLOOD
 HAZARD AREA. THE BASE FLOOD ELEVATION FOR THE PROPERTY
 IS 7' NAVD 88. THE CITY OF WEST PALM BEACH HAS ADOPTED
 A FLOOD ORDINANCE THAT REQUIRES A TWO (2) FOOT FREE
 BOARD. THIS MEANS THAT THE LOWEST FLOOR AND ALL
 EQUIPMENT SERVICING THE RESIDENCE IS REQUIRED TO BE AT
 OR ABOVE 9' NAVD 88. THE GARAGE AND STORAGE CAN BE
 BELOW BFE, IF FLOOD VENTS ARE INSTALLED AND NO
 MATERIALS OR EQUIPMENT THAT CAN BE DAMAGED BY FLOOD
 WATERS ARE BELOW BFE. SHOW COMPLIANCE WITH THESE
 REQUIREMENTS ON THE PLANS. SPECIFY ALL ELEVATIONS IN
 NAVD 88 ON ALL CONSTRUCTION DOCUMENTS, SUCH AS,
 SURVEYS, SITE PLANS, ARCHITECTURAL PLANS AND ELEVATION
 CERTIFICATES.
  
 4) THE STRUCTURAL PLANS ARE REQUIRED TO HAVE THE
 ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE IN THE TITLE
 BLOCK ON EACH SHEET. FAC 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 5) SPECIFY THE TERMITE PROTECTION THAT WILL BE PROVIDED
 ON THE PLANS. R318.1 TERMITE PROTECTION SHALL BE
 PROVIDED BY REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES
 APPLIED TO WOOD, OR OTHER APPROVED METHODS OF TERMITE
 PROTECTION LABELED FOR USE AS A PREVENTATIVE TREATMENT
 TO NEW CONSTRUCTION. SEE SECTION 202, ?REGISTERED
 TERMITICIDE.? UPON COMPLETION OF THE APPLICATION OF THE
 TERMITE PROTECTIVE TREATMENT, A CERTIFICATE OF
 COMPLIANCE SHALL BE ISSUED TO THE BUILDING DEPARTMENT
 BY THE LICENSED PEST CONTROL COMPANY THAT CONTAINS THE
 FOLLOWING STATEMENT: ?THE BUILDING HAS RECEIVED A
 COMPLETE TREATMENT FOR THE PREVENTION OF SUBTERRANEAN
 TERMITES. TREATMENT IS IN ACCORDANCE WITH RULES AND
 LAWS ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 6) PROVIDE ACCURATE AREA TABULATIONS FOR THE EXISTING
 CONDITIONED AND UNCONDITIONED SPACE, AS WELL AS, THE
 PROPOSED SPACES. FBC 107.2.1
  
 7) BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL,
 ONE SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO
 PALM BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS
 WITH THE IMPACT FEE STAMP AND A COPY OF THE PAID
 RECEIPT MUST BE RETURNED TO THE CITY BUILDING
 DEPARTMENT BEFORE THE BUILDING PERMIT CAN BE ISSUED.
 FOR INFORMATION CALL PALM BEACH COUNTY IMPACT FEES AT
 (561) 233-5025.
  
 8) SUBMIT ENERGY COMPLIANCE DOCUMENTS AS REQUIRED BY
 THE 2017 FBC ENERGY CONSERVATION SECTION R101.5.
  
 9) SHOW THAT THE DOOR FROM THE GARAGE TO THE DEN
 COMPLIES WITH FBC-R302.5.1
  
 10) IDENTIFY THE WINDOW AND DOOR TYPES ON THE PLANS.
 FBC 107.2.1
  
 11) PROVIDE THE CLEAR OPENING SIZE OF THE ACW 2828
 CASEMENT WINDOW IN BEDROOM #2 TO SHOW THAT IT COMPLIES
 WITH FBC-R310.1 FOR EMERGENCY ESCAPE AND RESCUE
 OPENINGS.
  
 12) SPECIFY SAFETY GLAZING FOR THE SHOWER ENCLOSURE,
 THE MASTER BATH WINDOW AT THE TUB AND THE WINDOWS IN
 THE SHOWERS IF THEY ARE WITHIN 60" OF THE SHOWER FLOOR.
 FBC-R308.4
  
 13) SHOW COMPLIANCE WITH FBC-R806.1 FOR ATTIC
 VENTILATION. ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN OR SNOW.
 VENTILATION OPENINGS SHALL HAVE A LEAST DIMENSION OF
 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH (6.4 MM)
 MAXIMUM. VENTILATION OPENINGS HAVING A LEAST DIMENSION
 LARGER THAN 1/4 INCH (6.4 MM) SHALL BE PROVIDED WITH
 CORROSION-RESISTANT WIRE CLOTH SCREENING, HARDWARE
 CLOTH OR SIMILAR MATERIAL WITH OPENINGS HAVING A LEAST
 DIMENSION OF 1/16 INCH (1.6 MM) MINIMUM AND 1/4 INCH
 (6.4 MM) MAXIMUM. OPENINGS IN ROOF FRAMING MEMBERS
 SHALL CONFORM TO THE REQUIREMENTS OF SECTION R802.7.
 REQUIRED VENTILATION OPENINGS SHALL OPEN DIRECTLY TO
 THE OUTSIDE AIR. R806.2 THE MINIMUM NET FREE
 VENTILATING AREA SHALL BE 1/150 OF THE AREA OF THE
 VENTED SPACE.
  
 14) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS. BUILDINGS
 WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION SHALL
 HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT HAVE A
 VERTICAL HEIGHT OF 30 INCHES OR GREATER OVER AN AREA OF
 NOT LESS THAN 30 SQUARE FEET. THE VERTICAL HEIGHT SHALL
 BE MEASURED FROM THE TOP OF THE CEILING FRAMING MEMBERS
 TO THE UNDERSIDE OF THE ROOF FRAMING MEMBERS. THE
 ROUGH-FRAMED OPENING SHALL BE NOT LESS THAN 22 INCHES
 BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE LOCATED IN
 A HALLWAY OR OTHER READILY ACCESSIBLE LOCATION. WHERE
 LOCATED IN A WALL, THE OPENING SHALL BE NOT LESS THAN
 22 INCHES WIDE BY 30 INCHES HIGH. WHERE THE ACCESS IS
 LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED HEADROOM IN
 THE ATTIC SPACE SHALL BE 30 INCHES AT SOME POINT ABOVE
 THE ACCESS MEASURED VERTICALLY FROM THE BOTTOM OF
 CEILING FRAMING MEMBERS. SEE SECTION M1305.1.3 FOR
 ACCESS REQUIREMENTS WHERE MECHANICAL EQUIPMENT IS
 LOCATED IN ATTICS.
  
 15) CLARIFY THE MEANING OF (2) KSD AND (2) TSD ON SHEET
 S4.0 OF THE PLANS. FBC 107.2.1
  
 16) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT
 ROOFING MATERIALS, WINDOW (GLASS TYPES), STRUCTURAL
 MULLIONS AND EXTERIOR DOOR TYPES.
  
 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  