| 2018-07-13 14:24:26 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | | INSPECTION. | | | | | | | | | 1) SHEET FP 1 - THERE ARE NO INDICATORS FOR TWO | | | DIFFERENT HEAD TYPES NOTED ON THE DRAWING LAYOUT THAT | | | ARE NOT IN THE LEGEND, ONE IS A SOLID BLACK LARGE | | | CIRCLE AND THE OTHER IS A THIN LINE OUTER LARGE CIRCLE | | | AND SOLID CENTER SMALL CIRCLE. | | | | | | THESE HEAD SYMBOLS ARE NOT INDICATED IN THE LEGEND. | | | | | | PROVIDE THE CORRECTED SYMBOLS FOR FIRE INSPECTOR REVIEW | | | ON INSPECTION AND CLEARLY LIST AND IDENTIFY THESE HEAD | | | TYPES IN THE LEGEND ON A REVISION. | | | | | | | | | | | | 2) THERE IS A SPRINKLER HEAD DRAWING NOTED WHICH IS | | | INDICATED AS SIN VK 494; HOWEVER, THE SPEC SHEET | | | INFORMATION ATTACHED TO THE PLANS APPEARS TO INDICATE | | | TYPES VK 462 & 463. | | | | | | PROVIDE THE COORECT SPEC SHEET AND OR SPRINKLER TYPE | | | FOR THE FIRE INSPECTOR ON INSPECTION. | | | | | | PLEASE REVIEW AND CORRECT AND ENSURE THE SUBMITTED | | | INFORMATION IS ACCURATE AND SPEC SHEETS MATCH AND | | | PROVIDE A REVISION. | | | | | | | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|