Plan Review Notes
Plan Review Notes For Permit 18070442
Permit Number 18070442
Review Stop B
Sequence Number 2
Notes
Date Text
2018-10-29 11:49:322ND REVIEW PASSED WITH PROVISOS
  
 RICHARD GATHRIGHT
 [email protected]
 561-805-6679
  
 1ST REVIEW BY SAMANTHA HILL
 9/4/2018 THAT GENERATED THE FOLLOWING COMMENTS
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY;
 APPLICABLE FOR BUILDING REVIEW. (PLUMBING APPROVED
 COMMENT CLOSED REG)
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS;
 APPLICABLE FOR BUILDING REVIEW. (FIRE APPROVED COMMENT
 CLOSED REG)
  
 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE
 PLAN, PLEASE PROVIDE:
 NOA 17?110602
 YKK 35H, FL 16554.1 & 16554.2
 YKK YES 50 FS, FL 14218.7
 (PRODUCT APPROVALS WERE PROVIDED COVER SHEETS PROVIDED
 BY REVIEWER COMMENT CLOSED OK REG)
  
 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES,
 TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502.
 (THIS COMMENT NOT PROPERLY ADDRESSED, SPACES SHOWN ON
 ALS1.1 MUST BE RELOCATED FOR THE OFFICE USE TO MEET THE
 FLORIDA ACCESSIBILITY REQUIREMENT,
 FAIR HOUSING REQUIREMENTS MUST ALSO BE MET. PROVIDE
 TOTAL NUMBER OF PARKING SPACES PROVIDED FOR THE COVERED
 UNITS IN THE BRISTOL AND PROVIDED LOCATIONS FOR THE
 REQUIRED PARKING REG)
  
 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE
 PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS
 ITEM DEFERRED, FBC 107.
 (NOTE ADDED TO SUBMIT NOA FOR APPROVAL, ITEM WILL BE A
 PROVISO REG)
  
 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE
 D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO
 THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION
 VIA EMAIL PRIOR TO RESUBMITTING. (ITEM HAS BEEN ADDED
 COMMENT CLOSED REG)
  
 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED
 MASONRY), PLEASE CORRECT. (COMMENT ON PLANS DELETED
 (RESOLVED) COMMENTCLOSED REG)
  
 8. OK (COMMENT MODIFIED IN FIRST REVIEW CLOSED REG)
  
 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014.
 PLEASE CHECK ALL PAGES AND UPDATE. (REFERENCES HAVE
 BEEN UPDATED COMMENT CLOSED REG)
  
 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF
 (?38.5, ?67.1, ?67.1). PRESSURES ARE FOR 20SF. AT THIS
 TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE
 PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES
 FOR 10 SF ARE REQUIRED.
 (ROOF PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG)
  
 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE.
 PARAPET IS TO BE 3? OR GREATER TO UTILIZE ZONE 2
 PRESSURES IN ZONE 3, FBC B 1609, ASCE7?10. (ROOF
 PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG)
  
 12. 6?S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B
 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE
 PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE
 EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES.
 (DETAILS 3 & 4 PG S3.2 STILL SAY CDX. THE REFERENCE ON
 THE ARCHITECTURAL SUCH AS DETAIL 4 ON A4.0.1 DOES NOT
 SAY FIRE RETARDANT LUMBER AS REQUIRED FOR A TYPE IIB AS
 STATED ON ALS1.1. THESE CORRECTIONS CAN BE A PROVISO
 REG)
  
 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC
 B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM
 PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE).(SITE
 PLAN PROVIDE GC-001 AND SURVEY PROVIDE IN SUBMITTAL
 18100459 COMMENT CLOSED REG)
  
 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION
 OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS
 PARCEL IS AFFECTED BY BOTH THE 6? AND 7? NAVD88 FLOOD
 ZONES. ALTERNATIVELY, P
 PLEASE ACKNOWLEDGE ON THE PLANS THAT THIS IS LOCATED IN
 SFHA 7? NAVD88. (SURVEY PROVIDE IN SUBMITTAL 18100459
 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE 6?AND 7?
 NAVD88 FLOOD ZONES COMMENT CLOSED REG)
  
 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE
 A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE. (AN
 EC WAS PROVIDED WITH SURVEY PROVIDE IN SUBMITTAL
 18100459 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE
 6?AND 7? NAVD88 FLOOD ZONES.
 EC SUBMITTED WAS NOT CORRECT, EC WAS UNDER CONSTRUCTION
 AND ONLY LOCATED TOP OF FOOTERS IT DID NOT KNOWLEDGE
 PROPOSED FLOOR ELEVATION.EC ALSO HAD NOTATION OF FLOOD
 VENTS. RICHARD DEAN OF DEAN SURVEYING WAS CONTACTED
 CONCERNING THE FLOOD VENTS AND NOT HAVING A PROPOSED
 EC.
 HE STATED HE USED THE GARAGE DOOR OPENINGS AS FLOOD
 OPENINGS. MR. DEAN SAID HE WOULD PROVIDE A PROPER
 PROPOSED EC AND PROVIDE AN UNDER CONSTRUCTION EC
 SHOWING FLOOR ELEVATION. THE EC DATED 10/01/18 HE SAID
 IS NOT CORRECT AND HE WILL VOID THAT DOCUMENT. R DEAN
 SAID HE WOULD HAVE THE CORRECTED EC BY 11/02/18.
 COMMENT NOT CLOSED HOWEVER IT WILL BE A PROVISO REG)
  
 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR
 STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00
 APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY
 WITH THE REQUIREMENT OF 9? NAVD88. ON A AND/OR SSHEETS,
 PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH THE
 FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION. (FLOOR
 ELEVATIONS WERE ADDED AND SURVEYOR WILL PROVIDE SURVEY
 TO SUPPORT SUCH COMMENT CLOSED REG)
  
 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED
 STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD
 AREA,DESIGN FLOOD ELEVATION IS BFE + 2? FREEBOARD.(THE
 ENTIRE BUILDING IS AT ELEVATION 9.00 NAVD88 COMMENT
 CLOSED REG)
  
 18. ENERGY CALCS REQURIED, FBC EC C401. (ENERGY CALCS
 SUBMITTED COMMENT CLOSED REG)
  
 19. THIS PERMIT WILL BE ISSUED WITH PROVISO:
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE IS REQUIRED. EC
 THAT HAS BEEN SUBMITTED NEEDS CORRECTION. CORRECT EC
 MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 AN UNDER CONSTRUCTION EC IS REQUIRED TO ESTABLISH FLOOR
 HEIGHT. PRIOR TO FINAL INSPECTION BUT AFTER ALL
 MECHANICAL EQUIPMENT HAS BEEN INSTALLED AND FINAL
 GRADES COMPLETED,
 A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE
 REQUIRED. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY
 REVIEW.
 B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT ?
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF
 RECORD ARE TO BE SUBMITTED TO THE BUILDING DIVISION,
 REVIEWED AND ISSUED PRIOR TO
 INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES
 SPECIFIED BY SEOR PRIOR TO SUBMITTAL.
 IF PRODUCT APPROVAL OFFERS OPTIONS, INDICATE OPTION
 PROPOSED, ESPECIALLY IF NOT ALL
 OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES.
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR
 THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS CONTROL
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
  
  