| 2018-10-29 11:49:32 | 2ND REVIEW PASSED WITH PROVISOS |
| | |
| | RICHARD GATHRIGHT |
| | [email protected] |
| | 561-805-6679 |
| | |
| | 1ST REVIEW BY SAMANTHA HILL |
| | 9/4/2018 THAT GENERATED THE FOLLOWING COMMENTS |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY; |
| | APPLICABLE FOR BUILDING REVIEW. (PLUMBING APPROVED |
| | COMMENT CLOSED REG) |
| | |
| | 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS; |
| | APPLICABLE FOR BUILDING REVIEW. (FIRE APPROVED COMMENT |
| | CLOSED REG) |
| | |
| | 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE |
| | PLAN, PLEASE PROVIDE: |
| | NOA 17?110602 |
| | YKK 35H, FL 16554.1 & 16554.2 |
| | YKK YES 50 FS, FL 14218.7 |
| | (PRODUCT APPROVALS WERE PROVIDED COVER SHEETS PROVIDED |
| | BY REVIEWER COMMENT CLOSED OK REG) |
| | |
| | 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES, |
| | TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502. |
| | (THIS COMMENT NOT PROPERLY ADDRESSED, SPACES SHOWN ON |
| | ALS1.1 MUST BE RELOCATED FOR THE OFFICE USE TO MEET THE |
| | FLORIDA ACCESSIBILITY REQUIREMENT, |
| | FAIR HOUSING REQUIREMENTS MUST ALSO BE MET. PROVIDE |
| | TOTAL NUMBER OF PARKING SPACES PROVIDED FOR THE COVERED |
| | UNITS IN THE BRISTOL AND PROVIDED LOCATIONS FOR THE |
| | REQUIRED PARKING REG) |
| | |
| | 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE |
| | PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS |
| | ITEM DEFERRED, FBC 107. |
| | (NOTE ADDED TO SUBMIT NOA FOR APPROVAL, ITEM WILL BE A |
| | PROVISO REG) |
| | |
| | 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE |
| | D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO |
| | THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION |
| | VIA EMAIL PRIOR TO RESUBMITTING. (ITEM HAS BEEN ADDED |
| | COMMENT CLOSED REG) |
| | |
| | 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED |
| | MASONRY), PLEASE CORRECT. (COMMENT ON PLANS DELETED |
| | (RESOLVED) COMMENTCLOSED REG) |
| | |
| | 8. OK (COMMENT MODIFIED IN FIRST REVIEW CLOSED REG) |
| | |
| | 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014. |
| | PLEASE CHECK ALL PAGES AND UPDATE. (REFERENCES HAVE |
| | BEEN UPDATED COMMENT CLOSED REG) |
| | |
| | 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF |
| | (?38.5, ?67.1, ?67.1). PRESSURES ARE FOR 20SF. AT THIS |
| | TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE |
| | PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES |
| | FOR 10 SF ARE REQUIRED. |
| | (ROOF PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG) |
| | |
| | 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE. |
| | PARAPET IS TO BE 3? OR GREATER TO UTILIZE ZONE 2 |
| | PRESSURES IN ZONE 3, FBC B 1609, ASCE7?10. (ROOF |
| | PRESSURES HAVE BEEN REVISED COMMENT CLOSED REG) |
| | |
| | 12. 6?S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B |
| | 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE |
| | PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE |
| | EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES. |
| | (DETAILS 3 & 4 PG S3.2 STILL SAY CDX. THE REFERENCE ON |
| | THE ARCHITECTURAL SUCH AS DETAIL 4 ON A4.0.1 DOES NOT |
| | SAY FIRE RETARDANT LUMBER AS REQUIRED FOR A TYPE IIB AS |
| | STATED ON ALS1.1. THESE CORRECTIONS CAN BE A PROVISO |
| | REG) |
| | |
| | 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC |
| | B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM |
| | PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE).(SITE |
| | PLAN PROVIDE GC-001 AND SURVEY PROVIDE IN SUBMITTAL |
| | 18100459 COMMENT CLOSED REG) |
| | |
| | 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION |
| | OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS |
| | PARCEL IS AFFECTED BY BOTH THE 6? AND 7? NAVD88 FLOOD |
| | ZONES. ALTERNATIVELY, P |
| | PLEASE ACKNOWLEDGE ON THE PLANS THAT THIS IS LOCATED IN |
| | SFHA 7? NAVD88. (SURVEY PROVIDE IN SUBMITTAL 18100459 |
| | THAT DEPICTS LOCATION OF BUILDING IN BOTH THE 6?AND 7? |
| | NAVD88 FLOOD ZONES COMMENT CLOSED REG) |
| | |
| | 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE |
| | A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE. (AN |
| | EC WAS PROVIDED WITH SURVEY PROVIDE IN SUBMITTAL |
| | 18100459 THAT DEPICTS LOCATION OF BUILDING IN BOTH THE |
| | 6?AND 7? NAVD88 FLOOD ZONES. |
| | EC SUBMITTED WAS NOT CORRECT, EC WAS UNDER CONSTRUCTION |
| | AND ONLY LOCATED TOP OF FOOTERS IT DID NOT KNOWLEDGE |
| | PROPOSED FLOOR ELEVATION.EC ALSO HAD NOTATION OF FLOOD |
| | VENTS. RICHARD DEAN OF DEAN SURVEYING WAS CONTACTED |
| | CONCERNING THE FLOOD VENTS AND NOT HAVING A PROPOSED |
| | EC. |
| | HE STATED HE USED THE GARAGE DOOR OPENINGS AS FLOOD |
| | OPENINGS. MR. DEAN SAID HE WOULD PROVIDE A PROPER |
| | PROPOSED EC AND PROVIDE AN UNDER CONSTRUCTION EC |
| | SHOWING FLOOR ELEVATION. THE EC DATED 10/01/18 HE SAID |
| | IS NOT CORRECT AND HE WILL VOID THAT DOCUMENT. R DEAN |
| | SAID HE WOULD HAVE THE CORRECTED EC BY 11/02/18. |
| | COMMENT NOT CLOSED HOWEVER IT WILL BE A PROVISO REG) |
| | |
| | 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR |
| | STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00 |
| | APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY |
| | WITH THE REQUIREMENT OF 9? NAVD88. ON A AND/OR SSHEETS, |
| | PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH THE |
| | FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION. (FLOOR |
| | ELEVATIONS WERE ADDED AND SURVEYOR WILL PROVIDE SURVEY |
| | TO SUPPORT SUCH COMMENT CLOSED REG) |
| | |
| | 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED |
| | STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD |
| | AREA,DESIGN FLOOD ELEVATION IS BFE + 2? FREEBOARD.(THE |
| | ENTIRE BUILDING IS AT ELEVATION 9.00 NAVD88 COMMENT |
| | CLOSED REG) |
| | |
| | 18. ENERGY CALCS REQURIED, FBC EC C401. (ENERGY CALCS |
| | SUBMITTED COMMENT CLOSED REG) |
| | |
| | 19. THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| | A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER |
| | CONSTRUCTION" ELEVATION CERTIFICATE IS REQUIRED. EC |
| | THAT HAS BEEN SUBMITTED NEEDS CORRECTION. CORRECT EC |
| | MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW. |
| | AN UNDER CONSTRUCTION EC IS REQUIRED TO ESTABLISH FLOOR |
| | HEIGHT. PRIOR TO FINAL INSPECTION BUT AFTER ALL |
| | MECHANICAL EQUIPMENT HAS BEEN INSTALLED AND FINAL |
| | GRADES COMPLETED, |
| | A "FINISHED CONSTRUCTION" ELEVATION CERTIFICATE WILL BE |
| | REQUIRED. THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY |
| | REVIEW. |
| | B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT ? |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF |
| | RECORD ARE TO BE SUBMITTED TO THE BUILDING DIVISION, |
| | REVIEWED AND ISSUED PRIOR TO |
| | INSTALLATION. CONFIRM COMPLIANCE WITH PRESSURES |
| | SPECIFIED BY SEOR PRIOR TO SUBMITTAL. |
| | IF PRODUCT APPROVAL OFFERS OPTIONS, INDICATE OPTION |
| | PROPOSED, ESPECIALLY IF NOT ALL |
| | OPTIONS COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR |
| | THE FOLLOWING ITEMS AS APPLICABLE: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS CONTROL |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | |
| | |