2018-07-31 12:38:341) SUBMIT DOCUMENTATION AS TO HOW THE STORM DRAINAGE
 WAS SIZED. THE SYSTEM SHALL BE SIZED IN ACCORDANCE WITH
 THE 2017 FBC-PLUMBING SECS.1105.2, 1106.1, 1106.2,
 1106.3.
 2) SHT. A8.0.1 - DETAIL #1 - THE WATER CLOSET SHALL BE
 LOCATED IN ACCORDANCE WITH THE 2017 FBC- ACCESSIBILITY
 SEC.604.2.
 3) THE REAR GRAB BAR SHALL BE LOCATED IN ACCORDANCE
 WITH 2017 FBC- ACCESS. SEC.604.5.2.
 4) SHOW THE CLEAR INSIDE LENGTH AND WIDTH DIMENSIONS OF
 THE TOILET ROOM ON SHT. A8.0.1. WPB AMEND. TO FBC SEC.
 107.2.1.
 5) SHOW THE REQUIRED CLEAR FLOOR SPACE FOR THE WATER
 CLOSET AND THE LAVATORY. COMPLY WITH 2017 FBC-ACCESS.
 SECS. 604.3, 606.2.
 6) SHOW THE REQUIRED KNEE AND TOE CLEARANCES FFOR THE
 LAVATORY PER THE 2017 FBC-ACCESS. SEC. 306.
 7) SHT. A8.0.1 - THE LOCATION OF THE MIRROR SHALL
 COMPLY WITH 2017 FBC-SEC.603.3.
 8) SHOW THE LOCATION OF THE BABAY CHANGING STATION ON
 THE FLOOR PLAN.
 9) THE DOOR FOR THE TOILET ROOM APPEARS TO SWING INTO
 THE CLEAR FLOOR SPACE FOR THE LAVATORY. COMPLY WITH
 2017 FBC-ACCESS. SEC.603.2.3.
 10) SHT. P0.1 - THE ISOMETRIC OF THE ROOF DRAINAGE
 SYSTEM DOES NOT CORRELATE WITH THE PLAN VIEW ON SHT.
 P2.2. CLARIFY.
 11) A BACKFLOW PREVENTION DEVICE IS REQUIRED ON THE
 DOMESTIC WATER AND THE IRRIGATION SYSTEM FOR THIS
 STRUCTURE PER THE CITY OF WPB UTILITIES DEPT. CROSS
 CONNECTION CONTROL MANUAL.
 12) A SEPARATE PLUMBING PERMIT WILL BE REQUIRED FOR THE
 BACKFLOW DEVICES.
 13) SUBMIT A DETAIL FOR THE TERMINATION OF THE
 CONDENSATE DRAIN. THE PLAN STATES THEY DISCHARGE TO A
 GREEN AREA.WPB AMEND. TO FBC SEC. 107.2.1.
  