| 2018-08-15 09:16:31 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070442 |
| | 8/15/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION. |
| | . |
| | |
| | 2) ENERGY EFFICIENCY COMPLIANCE IS REQUIRED FOR THE |
| | CONDITIONED OFFICE PORTION OF THE NEW PARKING GARAGE |
| | BUILDING. PLEASE SEE SECTIONS C101.5 & C401.1 FBC EC |
| | AND SUBMIT A COMPLIANCE REPORT. |
| | |
| | 3) M6.1: PLEASE PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR THE PARKING GARAGE IN COMPLIANCE WITH |
| | SECTION 404.2 FBC M. |
| | |
| | 404.2 MINIMUM VENTILATION. AUTOMATIC OPERATION OF THE |
| | SYSTEM SHALL NOT REDUCE THE VENTILATION AIRFLOW RATE |
| | BELOW 0.05 CFM PER SQUARE FOOT (0.00025 M3/S ? M2) OF |
| | THE FLOOR AREA AND THE SYSTEM SHALL BE CAPABLE OF |
| | PRODUCING A VENTILATION AIRFLOW RATE OF 0.75 CFM PER |
| | SQUARE FOOT (0.0038 M3/S ? M2) OF FLOOR AREA. |
| | |
| | 4) SITE SPECIFIC WIND LOAD ENGINEERING AND FL. PRODUCT |
| | APPROVALS AND/OR MIAMI-DADE NOA'S ARE REQUIRED FOR |
| | INSTALLATION OF THE ROOF TOP EXHAUST FANS, CONDENSER |
| | UNIT, AND THE GARAGE AIR INTAKE LOUVERS - SECTION |
| | 301.15 FBC M, AND RULE 9N-3 FAC. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CO AND |
| | NO2 SENSORS- SECTION 304.1 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |