2018-08-13 16:59:20FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) PANEL "A" IS FEEDING COMMUNITY CENTER, PLEASE SHOW
 LOCATION.
  
 2) AIC RATINGS FOR THE SERVICE IS REQUIRED SHOW
 CALCULATIONS
  
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 AND DOWNSTREAM
 PANELS IS ADEQUATE. NEC 110.9, 110.10
  
 3) MAIN IS 1200A NEEDS TO COMPLY WITH 240.87
  
 240.87 ARC ENERGY REDUCTION
 WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR
 WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A
 CIRCUIT BREAKER IS RATED
 OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND
 (B) SHALL APPLY.
  
 (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO
 THOSE AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR
 INSPECT THE INSTALLATION
 AS TO THE LOCATION OF THE CIRCUIT BREAKER(S)
 .
 (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE
 FOLLOWING OR APPROVED EQUIVALENT MEANS SH ALL BE
 PROVIDED:
 (1) ZONE-SELECTIVE INTERLOCKING
 (2) DIFFERENTIAL RELAYING
 (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL
 STATUS INDICATOR
 (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM
 (5) AN APPROVED EQUIVALENT MEANS