| 2018-08-13 16:59:20 | FLORIDA BUILDING CODE 2017 6TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED |
| | NFPA 70 2014 EDITION |
| | |
| | JAKE LEAHY |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | 1) PANEL "A" IS FEEDING COMMUNITY CENTER, PLEASE SHOW |
| | LOCATION. |
| | |
| | 2) AIC RATINGS FOR THE SERVICE IS REQUIRED SHOW |
| | CALCULATIONS |
| | |
| | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE |
| | AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO |
| | CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT |
| | AND DOWNSTREAM |
| | PANELS IS ADEQUATE. NEC 110.9, 110.10 |
| | |
| | 3) MAIN IS 1200A NEEDS TO COMPLY WITH 240.87 |
| | |
| | 240.87 ARC ENERGY REDUCTION |
| | WHERE THE HIGHEST CONTINUOUS CURRENT TRIP SETTING FOR |
| | WHICH THE ACTUAL OVERCURRENT DEVICE INSTALLED IN A |
| | CIRCUIT BREAKER IS RATED |
| | OR CAN BE ADJUSTED IS 1200 A OR HIGHER, 240.87(A) AND |
| | (B) SHALL APPLY. |
| | |
| | (A) DOCUMENTATION. DOCUMENTATION SHALL BE AVAILABLE TO |
| | THOSE AUTHORIZED TO DESIGN, INSTA LL, OPERATE, OR |
| | INSPECT THE INSTALLATION |
| | AS TO THE LOCATION OF THE CIRCUIT BREAKER(S) |
| | . |
| | (B) METHOD TO REDUCE CLEARING TIME. ONE OF THE |
| | FOLLOWING OR APPROVED EQUIVALENT MEANS SH ALL BE |
| | PROVIDED: |
| | (1) ZONE-SELECTIVE INTERLOCKING |
| | (2) DIFFERENTIAL RELAYING |
| | (3) ENERGY-REDUCING MAINTENANCE SWITCHING WITH LOCAL |
| | STATUS INDICATOR |
| | (4) ENERGY-REDUCING ACTIVE ARC FLASH MITIGATION SYSTEM |
| | (5) AN APPROVED EQUIVALENT MEANS |