Plan Review Notes
Plan Review Notes For Permit 18070442
Permit Number 18070442
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-27 12:22:47****CORRECTIONS****
 REVISED 9/4/18 (REMOVED COMMENT #8)
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY;
 APPLICABLE FOR BUILDING REVIEW.
  
 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS;
 APPLICABLE FOR BUILDING REVIEW.
  
 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE
 PLAN, PLEASE PROVIDE:
  
 NOA 17-8080.06
 YKK 35H, FL 16554.1 & 16554.2
 YKK YES 50 FS, FL 14218.7
  
 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES,
 TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502.
  
 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE
 PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS
 ITEM DEFERRED, FBC 107.
  
 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE
 D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO
 THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION
 VIA EMAIL PRIOR TO RESUBMITTING.
  
 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED
 MASONRY), PLEASE CORRECT.
  
 8. OK
  
 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014.
 PLEASE CHECK ALL PAGES AND UPDATE.
  
 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF
 (-38.5, -67.1, -67.1). PRESSURES ARE FOR 20SF. AT THIS
 TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE
 PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES
 FOR 10 SF ARE REQUIRED.
  
 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE.
 PARAPET IS TO BE 3' OR GREATER TO UTILIZE ZONE 2
 PRESSURES IN ZONE 3, FBC B 1609, ASCE7-10.
  
 12. 6-S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B
 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE
 PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE
 EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES.
  
 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC
 B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM
 PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE).
  
 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION
 OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS
 PARCEL IS AFFECTED BY BOTH THE 6' AND 7' NAVD88 FLOOD
 ZONES. ALTERNATIVELY, PLEASE ACKNOWLEDGE ON THE PLANS
 THAT THIS IS LOCATED IN SFHA 7' NAVD88.
  
 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE
 A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE.
  
 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR
 STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00
 APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY
 WITH THE REQUIREMENT OF 9' NAVD88. ON A AND/OR S
 SHEETS, PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH
 THE FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION.
  
 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED
 STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD AREA,
 DESIGN FLOOD ELEVATION IS BFE + 2' FREEBOARD.
  
 18. ENERGY CALCS REQURIED, FBC EC C401.
  
 19. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED.
 THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL
 EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES
 COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW.
  
 B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT -
 COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY
 DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING
 DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 CONFIRM COMPLIANCE WITH PRESSURES SPECIFIED BY SEOR
 PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS,
 INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS
 COMPLY WITH MINIMUM DESIGN PRESSURES.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  
 D. AIPP COMPLIANCE MAY BE REQUIRED; VERIFICATION
 REQUIRED PRIOR TO C.O.
  
 *******************************
 INTERNAL USE ONLY:
 USC-404 321 - NEW: PARKING GARAGE
 SQUARE FEET - 19,924
  
 CONSTRUCTION TYPE: IIB
  
 FLOORS: 1
 BEDROOMS:
 ROOMS:
 SQ FT LIVABLE: 19924
 SQ FT FOOTPRINT: 19924
 SQ FT ROOF: 19924
  
 SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF
 KNOWN):
 SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN):
 XX.XX
 SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN:
 XX.XX
 OCC LOAD:
 PROP USE: APARTMENT
 SPRINKLER SYS? Y
 SPRK REQ'D? Y
 BATHRMS:
  
 BLDG CODE: FL 2017
 OCC CLASS: 6TH ED S-1
  
  