| 2018-08-27 12:22:47 | ****CORRECTIONS**** |
| | REVISED 9/4/18 (REMOVED COMMENT #8) |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY; |
| | APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 2. SEE FIRE COMMENTS REGARDING FIRE SPRINKLERS; |
| | APPLICABLE FOR BUILDING REVIEW. |
| | |
| | 3. SINCE THE PRODUCT APPROVALS ARE SPECIFIED ON THE |
| | PLAN, PLEASE PROVIDE: |
| | |
| | NOA 17-8080.06 |
| | YKK 35H, FL 16554.1 & 16554.2 |
| | YKK YES 50 FS, FL 14218.7 |
| | |
| | 4. REVISE PLAN TO STATE TOTAL NUMBER OF PARKING SPACES, |
| | TOTAL NUMBER OF ACCESSIBLE SPACES, FBC A 208.2, 502. |
| | |
| | 5. CONDENSING UNIT STAND SHOWN ON S4.0; EITHER PROVIDE |
| | PRODUCT APPROVAL OR INDICATE THAT YOU WOULD LIKE THIS |
| | ITEM DEFERRED, FBC 107. |
| | |
| | 6. S0.0, S6.1, THIS APPEARS TO BE LOCATED IN EXPOSURE |
| | D, FBC B 1609. PLEASE NOTE THE FETCH OF OVER A MILE TO |
| | THE SOUTH. IF SEOR DISAGREES, PLEASE SEND JUSTIFICATION |
| | VIA EMAIL PRIOR TO RESUBMITTING. |
| | |
| | 7. S0.0 HAS TEXT WHICH IS NOT LEGIBLE (REINFORCED |
| | MASONRY), PLEASE CORRECT. |
| | |
| | 8. OK |
| | |
| | 9. S0.1, S6.1, PAGES INCLUDE REFERENCES TO FBC 2014. |
| | PLEASE CHECK ALL PAGES AND UPDATE. |
| | |
| | 10. S0.1, ROOF PRESSURES APPEAR TOO LOW FOR A FLAT ROOF |
| | (-38.5, -67.1, -67.1). PRESSURES ARE FOR 20SF. AT THIS |
| | TIME I DO NOT KNOW THE FASTENING PROPOSED FOR THE |
| | PITCHED AND FLAT ROOFS, BUT IT APPEARS THAT PRESSURES |
| | FOR 10 SF ARE REQUIRED. |
| | |
| | 11. CLARIFY PARAPET HEIGHT RELATIVE TO ROOF SURFACE. |
| | PARAPET IS TO BE 3' OR GREATER TO UTILIZE ZONE 2 |
| | PRESSURES IN ZONE 3, FBC B 1609, ASCE7-10. |
| | |
| | 12. 6-S3.2 SHOWS WOOD TRUSSES, CDX PLYWOOD. SEE FBC B |
| | 603 (COMBUSTIBLES IN TYPE I & II BUILDINGS), REVISE |
| | PLAN TO SHOW COMPLIANCE (FRT OR STATE APPLICABLE |
| | EXCEPTION); CHECK ALL DETAILS FOR COMBUSTIBLES. |
| | |
| | 13. PROVIDE A SITE PLAN WHICH SHOWS COMPLIANCE WITH FBC |
| | B TABLES 602, 705.8 (IN PARTICULAR, THE DISTANCE FROM |
| | PROPOSED STRUCTURE TO THE SOUTH PROPERTY LINE). |
| | |
| | 14. FBC B 107.2.5, PROVIDE A PLAN WHICH SHOWS LOCATION |
| | OF STRUCTURE RELATIVE TO THE FLOOD ZONE LINES. THIS |
| | PARCEL IS AFFECTED BY BOTH THE 6' AND 7' NAVD88 FLOOD |
| | ZONES. ALTERNATIVELY, PLEASE ACKNOWLEDGE ON THE PLANS |
| | THAT THIS IS LOCATED IN SFHA 7' NAVD88. |
| | |
| | 15. IF LOCATED IN A SFHA, FBC B 107.3.5.1.1(1), PROVIDE |
| | A "CONSTRUCTION DOCUMENTS" ELEVATION CERTIFICATE. |
| | |
| | 16. FBC B 107.2.5, REVISE ARCHITECTURAL AND/OR |
| | STRUCTURAL PLANS TO INCLUDE PROPOSED ELEVATION. C5.00 |
| | APPEARS TO PROPOSE 10.52 NGVD29. THIS APPEARS TO COMPLY |
| | WITH THE REQUIREMENT OF 9' NAVD88. ON A AND/OR S |
| | SHEETS, PLEASE SPECIFY IN NAVD88 TO BE CONSISTENT WITH |
| | THE FLOOD INSURANCE RATE MAPS OR SPECIFY CONVERSION. |
| | |
| | 17. FBC B 1612, IF ANY PORTION OF THE PROPOSED |
| | STRUCTURE IS LOCATED IN THE SPECIAL FLOOD HAZARD AREA, |
| | DESIGN FLOOD ELEVATION IS BFE + 2' FREEBOARD. |
| | |
| | 18. ENERGY CALCS REQURIED, FBC EC C401. |
| | |
| | 19. THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| | |
| | A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER |
| | CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW. |
| | PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL |
| | EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES |
| | COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION |
| | CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA |
| | EMAIL FOR PRELIMINARY REVIEW. |
| | |
| | B. DEFERRED SUBMITTALS REQUESTED BY ARCHITECT - |
| | COMPONENT & CLADDING PRODUCT APPROVALS REVIEWED BY |
| | DESIGNER OF RECORD ARE TO BE SUBMITTED TO THE BUILDING |
| | DIVISION, REVIEWED AND ISSUED PRIOR TO INSTALLATION. |
| | CONFIRM COMPLIANCE WITH PRESSURES SPECIFIED BY SEOR |
| | PRIOR TO SUBMITTAL. IF PRODUCT APPROVAL OFFERS OPTIONS, |
| | INDICATE OPTION PROPOSED, ESPECIALLY IF NOT ALL OPTIONS |
| | COMPLY WITH MINIMUM DESIGN PRESSURES. |
| | |
| | C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| | REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE: |
| | LIGHT POLES/SITE LIGHTING |
| | FIRE ALARM |
| | FIRE SPRINKLER |
| | LOW VOLTAGE |
| | ACCESS |
| | LANDSCAPING |
| | IRRIGATION |
| | ALL OTHER ITEMS OTHER THAN BMEP |
| | |
| | D. AIPP COMPLIANCE MAY BE REQUIRED; VERIFICATION |
| | REQUIRED PRIOR TO C.O. |
| | |
| | ******************************* |
| | INTERNAL USE ONLY: |
| | USC-404 321 - NEW: PARKING GARAGE |
| | SQUARE FEET - 19,924 |
| | |
| | CONSTRUCTION TYPE: IIB |
| | |
| | FLOORS: 1 |
| | BEDROOMS: |
| | ROOMS: |
| | SQ FT LIVABLE: 19924 |
| | SQ FT FOOTPRINT: 19924 |
| | SQ FT ROOF: 19924 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: |
| | PROP USE: APARTMENT |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: |
| | |
| | BLDG CODE: FL 2017 |
| | OCC CLASS: 6TH ED S-1 |
| | |
| | |