| 2018-10-04 13:52:44 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET P4; SHEET WAS SIGNED, BUT NOT SEALED |
| | BY THE ENGINEER OF RECORD- SECTION 61G15-23.002 FAC. |
| | 2. RE: PLAN SHEET P2.1; PLEASE PROVIDE MANUFACTURE |
| | SPECIFICATIONS FOR ITEM #8,THE WATER TREATMENT (RO) |
| | SYSTEM (SECOND REQUEST). WPB FBC 107.2.1 |
| | 3. RE: PLAN SHEET P2.1; PROVIDE NOTE AT RPZ INDICATING |
| | THE RELIEF OUTLET SHALL DISCHARGE THROUGH AN AIR GAP TO |
| | THE FLOOR SINK IN ACCORDANCE WITH FBC PL 608.13.2. WPB |
| | FBC 107.2.1 |
| | 4. RE: PLAN SHEET P2.1; SCHEMATIC AND FLOOR PLAN SHOWS |
| | WHAT APPEAR SYMBOLS FOR A CHECK VALVE. ARE THESE CHECK |
| | VALVES OR BACKFLOW PREVENTORS? IF BACKFLOW PREVENTORS |
| | PLEASE INDICATE TYPE AND STANDARD SUCH AS ASSE 1022. IF |
| | IT IS THE INTENT TO PROTECT THE WATER SUPPLY TO ITEMS |
| | INCLUDING BUT NOT LIMITED TO THE CARBONATED BEVERAGE |
| | DISPENSERS AND COFFEE MAKERS WITH AN AIR GAP, THEN |
| | PROVIDE SPECS FOR THE UNIT THAT SHOW IT CAN BE DONE. |
| | NOTES REQUIRING AN INDIRECT WASTE BE RUN TO A FLOOR |
| | SINK THROUGH AN AIR GAP DOES NOT ADDRESS BACKFLOW |
| | CONNECTIONS IN THE WATER SUPPLY. AIR GAPS THAT ADDRESS |
| | SUCH CONNECTIONS ARE AS NOTED IN FPC PL 608.15.1. |
| | PLEASE CLARIFY. WPB FBC 107.2.1 |
| | 5. RE: PLAN SHEET P2.1; EQUIPMENT SCHEDULE, ITEM #204. |
| | THE ENGINEER IS TO PROVIDE DETAILS AND SPECS FOR MIXING |
| | VALVE AND BACKFLOW PREVENTOR INCLUDING PIPING |
| | ARRANGEMENT AND VALVING IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF FBC PL AND WPB FBC. WPB FBC 107.2.1 |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | THE COMMENT RESPONSE LETTER NOTED ON THE TRANSMITTAL |
| | DID NOT APPEAR WHEN THIS REVIEW TOOK PLACE. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-805-6715 |