Plan Review Notes
Plan Review Notes For Permit 18070421
Permit Number 18070421
Review Stop B
Sequence Number 2
Notes
Date Text
2018-10-15 12:55:13****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FROM PREVIOUS LIST:
  
 SHEET CS, FBC B 1004, CLARIFY OCCUPANT LOAD OF 6
 EMPLOYEES, USE GROUP "KITCHEN".
  
 FBC B 302.1, DECLARE AN OCCUPANCY CLASSIFICATION. FBC B
 TABLE 1004.1.2, DECLARE AN OCCUPANT LOAD.
  
 2ND REVIEW - 17 SEATS AND 12 EMPLOYEES ARE NOTED. SEE
 FBC B 1004.1.2, ARE THE SEATS FIXED? IF THEY ARE,
 REVISE PLAN TO NOTE FIXED SEATING, PROVIDE DETAILS, AND
 SHOW COMPLIANCE WITH FBC A 902. IF THEY ARE NOT FIXED,
 REVISE IN ACCORDANCE WITH FBC B TABLE 1004.1.2.
  
 IT APPEARS THAT ARCHITECT IS CALCULATING OCCUPANTS AT
 60SF PER PERSON PLUS SEATS. IT APPEARS THAT 15SF PER
 PERSON SHOULD BE UTILIZED, SEE TABLE B 1004.1.2,
 ASSEMBLY WITHOUT FIXED SEATS. IF ARCHITECT DISAGREES,
 PLEASE CONTACT ME PRIOR TO RESUBMITTING.
  
  
  
  