| 2018-10-15 12:55:13 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FROM PREVIOUS LIST: | | | | | | SHEET CS, FBC B 1004, CLARIFY OCCUPANT LOAD OF 6 | | | EMPLOYEES, USE GROUP "KITCHEN". | | | | | | FBC B 302.1, DECLARE AN OCCUPANCY CLASSIFICATION. FBC B | | | TABLE 1004.1.2, DECLARE AN OCCUPANT LOAD. | | | | | | 2ND REVIEW - 17 SEATS AND 12 EMPLOYEES ARE NOTED. SEE | | | FBC B 1004.1.2, ARE THE SEATS FIXED? IF THEY ARE, | | | REVISE PLAN TO NOTE FIXED SEATING, PROVIDE DETAILS, AND | | | SHOW COMPLIANCE WITH FBC A 902. IF THEY ARE NOT FIXED, | | | REVISE IN ACCORDANCE WITH FBC B TABLE 1004.1.2. | | | | | | IT APPEARS THAT ARCHITECT IS CALCULATING OCCUPANTS AT | | | 60SF PER PERSON PLUS SEATS. IT APPEARS THAT 15SF PER | | | PERSON SHOULD BE UTILIZED, SEE TABLE B 1004.1.2, | | | ASSEMBLY WITHOUT FIXED SEATS. IF ARCHITECT DISAGREES, | | | PLEASE CONTACT ME PRIOR TO RESUBMITTING. | | | | | | | | | | | | |
|