2018-07-17 11:37:491ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070421
 7/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A3.0: PLEASE SHOW THE LOCATION OF THE TURBO
 CHEF OVEN ON THE EQUIPMENT FLOOR PLAN. IT IS #384 IN
 THE SCHEDULE.
  
 2) M1.0: A TYOE II HOOD IS REQUIRED FOR THE NEW TURBO
 CHEF OVEN- SEE SECTION 507.3 FBC M BELOW:
  
 507.3 TYPE II HOODS.
 TYPE II HOODS SHALL BE INSTALLED ABOVE DISHWASHERS AND
 APPLIANCES THAT PRODUCE HEAT OR MOISTURE AND DO NOT
 PRODUCE GREASE OR SMOKE AS A RESULT OF THE COOKING
 PROCESS, EXCEPT WHERE THE HEAT AND MOISTURE LOADS FROM
 SUCH APPLIANCES ARE INCORPORATED INTO THE HVAC SYSTEM
 DESIGN OR INTO THE DESIGN OF A SEPARATE REMOVAL SYSTEM.
 TYPE II HOODS SHALL BE INSTALLED ABOVE ALL APPLIANCES
 THAT PRODUCE PRODUCTS OF COMBUSTION AND DO NOT PRODUCE
 GREASE OR SMOKE AS A RESULT OF THE COOKING PROCESS.
 SPACES CONTAINING COOKING APPLIANCES THAT DO NOT
 REQUIRE TYPE II HOODS SHALL BE PROVIDED WITH EXHAUST AT
 A RATE OF 0.70 CFM PER SQUARE FOOT (0.00033 M3/S). FOR
 THE PURPOSE OF DETERMINING THE FLOOR AREA REQUIRED TO
 BE EXHAUSTED, EACH INDIVIDUAL APPLIANCE THAT IS NOT
 REQUIRED TO BE INSTALLED UNDER A TYPE II HOOD SHALL BE
 CONSIDERED AS OCCUPYING NOT LESS THAN 100 SQUARE FEET
 (9.3 M2). SUCH ADDITIONAL SQUARE FOOTAGE SHALL BE
 PROVIDED WITH EXHAUST AT A RATE OF 0.70 CFM PER SQUARE
 FOOT [.00356 M3/(S ? M2)].
  
 3) M1.0: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY
 SIDE OF THE RTU IN ACCORDANCE WITH SECTION 606.2.1 FBC
 M. PLACE A SYMBOL AT THE REQUIRED LOCATION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  