| 2018-07-17 11:37:49 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070421 |
| | 7/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET A3.0: PLEASE SHOW THE LOCATION OF THE TURBO |
| | CHEF OVEN ON THE EQUIPMENT FLOOR PLAN. IT IS #384 IN |
| | THE SCHEDULE. |
| | |
| | 2) M1.0: A TYOE II HOOD IS REQUIRED FOR THE NEW TURBO |
| | CHEF OVEN- SEE SECTION 507.3 FBC M BELOW: |
| | |
| | 507.3 TYPE II HOODS. |
| | TYPE II HOODS SHALL BE INSTALLED ABOVE DISHWASHERS AND |
| | APPLIANCES THAT PRODUCE HEAT OR MOISTURE AND DO NOT |
| | PRODUCE GREASE OR SMOKE AS A RESULT OF THE COOKING |
| | PROCESS, EXCEPT WHERE THE HEAT AND MOISTURE LOADS FROM |
| | SUCH APPLIANCES ARE INCORPORATED INTO THE HVAC SYSTEM |
| | DESIGN OR INTO THE DESIGN OF A SEPARATE REMOVAL SYSTEM. |
| | TYPE II HOODS SHALL BE INSTALLED ABOVE ALL APPLIANCES |
| | THAT PRODUCE PRODUCTS OF COMBUSTION AND DO NOT PRODUCE |
| | GREASE OR SMOKE AS A RESULT OF THE COOKING PROCESS. |
| | SPACES CONTAINING COOKING APPLIANCES THAT DO NOT |
| | REQUIRE TYPE II HOODS SHALL BE PROVIDED WITH EXHAUST AT |
| | A RATE OF 0.70 CFM PER SQUARE FOOT (0.00033 M3/S). FOR |
| | THE PURPOSE OF DETERMINING THE FLOOR AREA REQUIRED TO |
| | BE EXHAUSTED, EACH INDIVIDUAL APPLIANCE THAT IS NOT |
| | REQUIRED TO BE INSTALLED UNDER A TYPE II HOOD SHALL BE |
| | CONSIDERED AS OCCUPYING NOT LESS THAN 100 SQUARE FEET |
| | (9.3 M2). SUCH ADDITIONAL SQUARE FOOTAGE SHALL BE |
| | PROVIDED WITH EXHAUST AT A RATE OF 0.70 CFM PER SQUARE |
| | FOOT [.00356 M3/(S ? M2)]. |
| | |
| | 3) M1.0: PROVIDE A DUCT SMOKE DETECTOR IN THE SUPPLY |
| | SIDE OF THE RTU IN ACCORDANCE WITH SECTION 606.2.1 FBC |
| | M. PLACE A SYMBOL AT THE REQUIRED LOCATION. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |