| Plan Review Notes For Permit 18070416 |
| Permit Number |
18070416 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-23 15:18:40 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY PLUMBING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE TOTAL DYNAMIC HEAD CALCULATOR THAT IS ON SHEET 2 | | | OF THE PLANS DOES NOT PROVIDE THE ACTUAL FRICTION LOSS | | | FOR THE PIPE, FITTINGS AND VALVES. THE FRICTION LOSS | | | FOR THE FILTER, HEATER AND SALT SYSTEM WERE NOT | | | INCLUDED IN THE CALCULATIONS. FBC 107.2.1 | | | | | | 2) IT DOES NOT APPEAR THAT THE SPA WATER IS BEING | | | FILTERED. PLEASE CLARIFY. FBC 107.2.1 & FBC-R 4501.20 |
|