2018-07-23 15:18:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY PLUMBING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE TOTAL DYNAMIC HEAD CALCULATOR THAT IS ON SHEET 2
 OF THE PLANS DOES NOT PROVIDE THE ACTUAL FRICTION LOSS
 FOR THE PIPE, FITTINGS AND VALVES. THE FRICTION LOSS
 FOR THE FILTER, HEATER AND SALT SYSTEM WERE NOT
 INCLUDED IN THE CALCULATIONS. FBC 107.2.1
  
 2) IT DOES NOT APPEAR THAT THE SPA WATER IS BEING
 FILTERED. PLEASE CLARIFY. FBC 107.2.1 & FBC-R 4501.20