| Plan Review Notes For Permit 18070378 |
| Permit Number |
18070378 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-23 07:00:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, REVISE PLAN TO INCLUDE INFORMATION ABOUT | | | THE BUILDING - IS THIS A HIGH RISE? IF NOT, HOW MANY | | | STORIES? | | | | | | PLAN PROPOSES TO REMOVE WHAT APPEARS TO BE AN ELEVATOR | | | LOBBY. ARE THEY REQUIRED IN THIS BUILDING? IF NOT, ARE | | | THE ELEVATORS PRESSURIZED, AND IF NOT, WHAT EXEMPTION | | | ALLOWS FOR REMOVAL OF THE ELEVATOR LOBBY? | | | | | | IF REMOVAL OF A REQUIRED ELEVATOR LOBBY IS PROPOSED, | | | WHEN DOES APPLICANT PROPOSE TO RESTORE THIS? | | | | | | | | | |
|