| 2018-08-01 15:44:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070304 |
| | 8/1/2018 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE MECHANICAL PLANS SHALL BE ELECTRONICALLY SIGNED |
| | AND SEALED IN ACCORDANCE WITH SECTION 61G15-23.005 FAC. |
| | |
| | 2) PROVIDE A DETAIL INDICATING HOW THE NEW BLOWERS WOLL |
| | BE ANCHORED TO THE NEW SLABS- SECTION 304.1 FBC M. |
| | |
| | 3) PROVIDE A GUARDRAIL DETAIL SHOWING THE HEIGHT FROM |
| | THE ADJACENT WALKING SURFACE, AND THE SPACING OF THE |
| | RAILS- SECTIONS 1015.3 AND 1015.4 FBC B. |
| | |
| | 4) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES THE |
| | BLOWERS, THE STAINLESSS STEEL PIPING AND PVC PIPINGS. |
| | THE MOTORIZED VALVES, THE COUPLINGS AND FITTINGS, THE |
| | DEPEND-O-LOK, AND TORGUE WRENCH SETTING FOR BOLTING THE |
| | PIPE COUPLINGS AND FITTINGS- SECTION 304.1 FBC M. |
| | |
| | 5) PROVIDE A TOTAL JOB BALUE ON THE PERMIT APPLICATION- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |