2018-07-12 11:09:29PERMIT # 18070299
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1) PER NFPA 241 ? STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS,
 SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE
 SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN
 ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1:
 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 30 FEET.
 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 35 FEET.
 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 40 FEET.
 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM
 ADJACENT STRUCTURES BY AT LEAST 45 FEET.
  
 2) PLAN DOES NOT SHOW THE DISTANCE FROM THE TRAILER TO
 THE EXISTING DREYFOOS HALL BUILDING. BUT THE FEW
 DETAILS PROVIDED APPEAR TO INDICATE THAT THE REQUIRED
 SEPARATION IS NOT BEING MET.
 PLEASE RE-SUBMIT AND INCLUDE THE RELEVANT DETAILS
 SHOWING COMPLIANCE WITH THE ABOVE REQUIREMENTS.
  
 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVEL, EXIT STAIR DETAILS, INCLUDING HANDRAILS, ETC.
  
  
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL