| 2018-07-12 11:09:29 | PERMIT # 18070299 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | 1) PER NFPA 241 ? STANDARD FOR SAFEGUARDING | | | CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS, | | | SECTION 4.2 TEMPORARY CONSTRUCTION TRAILERS SHALL BE | | | SEPARATED FROM ADJACENT TRAILERS OR STRUCTURES IN | | | ACCORDANCE WITH TABLE 4.2.1. PER TABLE 4.2.1: | | | 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 30 FEET. | | | 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 35 FEET. | | | 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 40 FEET. | | | 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM | | | ADJACENT STRUCTURES BY AT LEAST 45 FEET. | | | | | | 2) PLAN DOES NOT SHOW THE DISTANCE FROM THE TRAILER TO | | | THE EXISTING DREYFOOS HALL BUILDING. BUT THE FEW | | | DETAILS PROVIDED APPEAR TO INDICATE THAT THE REQUIRED | | | SEPARATION IS NOT BEING MET. | | | PLEASE RE-SUBMIT AND INCLUDE THE RELEVANT DETAILS | | | SHOWING COMPLIANCE WITH THE ABOVE REQUIREMENTS. | | | | | | 3) PROVIDE A LIFE SAFETY PLAN SHOWING ALL EXIT SIGNS, | | | EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF | | | TRAVEL, EXIT STAIR DETAILS, INCLUDING HANDRAILS, ETC. | | | | | | | | | | | | SUE ELLEN CALDERON | | | ASSISTANT FIRE MARSHAL | | | [email protected] | | | |
|