2018-08-14 11:49:42MECHANICAL PROVISOS
 8/14/18
  
 1) COMMISSIONING OF THE COMMON AC SYSTEMS AND
 ELECTRICAL LIGHTING CONTROLS IS REQUIRED. FINAL REPORT
 SHALL BE PROVIDED TO THE OWNERSHIP OF THE BUILDING AND
 THE BUILDING DEPARTMENT PRIOR TO RECEIVING CERTIFICATE
 OF OCCUPANCY.
  
 2) ) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR
 THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING
 APPROVAL BY THE ENGINEER OF RECORD:
  
 A) SMOKE CONTROL FANS.
 B) FIRE AND FIRE/SMOKE DAMPERS.
 C) BAROMETRIC DAMPERS
 D) DUCT SMOKE DETECTORS
 E) AC ROOF AND DUCT STANDS, WALL BRACKETS
 F) EXHAUST AND OUTSIDE AIR LOUVERS
 G) C02 AND N02 SENSORS
 H) PIPING INSULATIONS
 I) ACCESS PANELS
 J) GENERATOR
 K) COMMERCIAL CLOTHES DRYERS
 L) COOKING APPLIANCES
 M) DUCT FIRE WRAPPING
 N) FIRESTOPPING AND FIRE CAULKING
 O) MANUFACTURER'S SPECIFICATIONS AND WIND LOAD
 ENGINEERING FOR THE EXTERIOR BARBECUE.
 P) STRUCTURAL DETAILS FOR ATTACHING THE AC UNITS AND
 INLINE FAN SUPPORTS TO THE SLAB.
 Q) WIND LOAD ENGINEERING FOR ALL ROOF TOP MOUNTED
 MECHANICAL EQUIPMENT- OAU'S, FANS AND FAN CURBS, AC
 STANDS, SUPPORTS ETC.
  
 3) SMOKE CONTROL SYSTEM TESTING PRIOR TO C/O
  