| 2018-08-14 11:49:42 | MECHANICAL PROVISOS | | | 8/14/18 | | | | | | 1) COMMISSIONING OF THE COMMON AC SYSTEMS AND | | | ELECTRICAL LIGHTING CONTROLS IS REQUIRED. FINAL REPORT | | | SHALL BE PROVIDED TO THE OWNERSHIP OF THE BUILDING AND | | | THE BUILDING DEPARTMENT PRIOR TO RECEIVING CERTIFICATE | | | OF OCCUPANCY. | | | | | | 2) ) THE FOLLOWING IS A LIST OF DEFERRED SUBMITTALS FOR | | | THE MECHANICAL PERMIT THAT WILL REQUIRE SHOP DRAWING | | | APPROVAL BY THE ENGINEER OF RECORD: | | | | | | A) SMOKE CONTROL FANS. | | | B) FIRE AND FIRE/SMOKE DAMPERS. | | | C) BAROMETRIC DAMPERS | | | D) DUCT SMOKE DETECTORS | | | E) AC ROOF AND DUCT STANDS, WALL BRACKETS | | | F) EXHAUST AND OUTSIDE AIR LOUVERS | | | G) C02 AND N02 SENSORS | | | H) PIPING INSULATIONS | | | I) ACCESS PANELS | | | J) GENERATOR | | | K) COMMERCIAL CLOTHES DRYERS | | | L) COOKING APPLIANCES | | | M) DUCT FIRE WRAPPING | | | N) FIRESTOPPING AND FIRE CAULKING | | | O) MANUFACTURER'S SPECIFICATIONS AND WIND LOAD | | | ENGINEERING FOR THE EXTERIOR BARBECUE. | | | P) STRUCTURAL DETAILS FOR ATTACHING THE AC UNITS AND | | | INLINE FAN SUPPORTS TO THE SLAB. | | | Q) WIND LOAD ENGINEERING FOR ALL ROOF TOP MOUNTED | | | MECHANICAL EQUIPMENT- OAU'S, FANS AND FAN CURBS, AC | | | STANDS, SUPPORTS ETC. | | | | | | 3) SMOKE CONTROL SYSTEM TESTING PRIOR TO C/O | | | |
|