| 2018-10-03 05:54:52 | 1) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION | | | OF THE GENERATOR IN RELATION TO BUILDING OPENINGS, | | | DISTANCE FROM THE STRUCTURE, ETC. 2017 FBC 107.2.1. | | | 2) THE 3/4 INCH PE TO THE EXISTING GAS LOADS IS | | | UNDERSIZED.THE ORIGINAL PLAN ON FILE WITH THE CITY | | | SHOWS THE LINE FROM THE OUTLET OF THE GAS METER GOING | | | INTO A TEE AND THE TOTAL LOAD BEING DISTRIBUTED BETWEEN | | | 2 - 3/4 INCH PE LINES WHICH MEETS CODE. ONE 3/4 INCH PE | | | LINE SERVING THE EXISTING BTU LOAD OF 1,697,000 WILL | | | NOT WORK PER TABLE 402..2 (22) OF THE FUEL GAS CODE.IF | | | ONE LINE IS TO SUPPLY THE EXISTING BTU LOAD, IT SHALL | | | BE 1 1/4 INCH PE. | | | 3) YOU HAVE SUBMITTED COPIESS OF AN EXISTING CITY | | | DRAWING TO WHICH YOU HAVE ADDED THE GENERATOR ONTO THE | | | DRWAING. THESE DOCUMENTS ARE FOR REFERENCE ONLY AND | | | CANNOT BE USED TO ADD APPLIANCES/ EQUIPMENT AND BE | | | SUBMITTED FOR PERMIT. REMOVE THESE DRAWINGS FROM THE | | | PERMIT PACKAGE. 2017 FBC SEC.107.2.1. | | | 4) THERE ARE COPIES OF 2 DIFFERENT GAS DRAWINGS IN THIS | | | SUBMITTAL. REMOVE ALL OLD GAS DRAWINGS AND COMBINE THE | | | DOCUMENTS INTO TWO FULL, COMPLETE SETS OF PLANS FOR | | | REVIEW. 2017 FBC SEC. 107.2.1. | | | 5) THE GENERATOR SHALL BE A MINIMUM OF 10 FEET FROM ANY | | | BUILDING OPENING INCLUDING SOFFIT VENTS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | | | | | | | | | | |
|