Plan Review Notes
Plan Review Notes For Permit 18070248
Permit Number 18070248
Review Stop G
Sequence Number 2
Notes
Date Text
2018-10-03 05:54:521) SUBMIT TWO COPIES OF A SURVEY SHOWING THE LOCATION
 OF THE GENERATOR IN RELATION TO BUILDING OPENINGS,
 DISTANCE FROM THE STRUCTURE, ETC. 2017 FBC 107.2.1.
 2) THE 3/4 INCH PE TO THE EXISTING GAS LOADS IS
 UNDERSIZED.THE ORIGINAL PLAN ON FILE WITH THE CITY
 SHOWS THE LINE FROM THE OUTLET OF THE GAS METER GOING
 INTO A TEE AND THE TOTAL LOAD BEING DISTRIBUTED BETWEEN
 2 - 3/4 INCH PE LINES WHICH MEETS CODE. ONE 3/4 INCH PE
 LINE SERVING THE EXISTING BTU LOAD OF 1,697,000 WILL
 NOT WORK PER TABLE 402..2 (22) OF THE FUEL GAS CODE.IF
 ONE LINE IS TO SUPPLY THE EXISTING BTU LOAD, IT SHALL
 BE 1 1/4 INCH PE.
 3) YOU HAVE SUBMITTED COPIESS OF AN EXISTING CITY
 DRAWING TO WHICH YOU HAVE ADDED THE GENERATOR ONTO THE
 DRWAING. THESE DOCUMENTS ARE FOR REFERENCE ONLY AND
 CANNOT BE USED TO ADD APPLIANCES/ EQUIPMENT AND BE
 SUBMITTED FOR PERMIT. REMOVE THESE DRAWINGS FROM THE
 PERMIT PACKAGE. 2017 FBC SEC.107.2.1.
 4) THERE ARE COPIES OF 2 DIFFERENT GAS DRAWINGS IN THIS
 SUBMITTAL. REMOVE ALL OLD GAS DRAWINGS AND COMBINE THE
 DOCUMENTS INTO TWO FULL, COMPLETE SETS OF PLANS FOR
 REVIEW. 2017 FBC SEC. 107.2.1.
 5) THE GENERATOR SHALL BE A MINIMUM OF 10 FEET FROM ANY
 BUILDING OPENING INCLUDING SOFFIT VENTS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  
  
  