| Plan Review Notes For Permit 18070221 |
| Permit Number |
18070221 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-08-02 06:57:03 | 1) THE SITE PLAN YOU HAVE SUBMITTED NOTES A PVB | | | BACKFLOW DEVICE ON THE DOMESTIC WATER, IRRIGATION AND | | | POOL AUTOFILL BUT YOU HAVE SUBMITTED SPECS FOR AN RPZ | | | AND A PVB DEVICE. THE SITE PLAN NEEDS TO BE CORRECTED | | | TO SHOW THE CORRECT DEVICES AND THEIR LOCATION. | | | 2) THE 720A PVB DEVICE IS NOT A LEAD FREE DEVICE AND | | | CANNOT BE INSTALLED ON THE AUTOFILL. THE WILKINS 420XL | | | IS A LEAD FREE DEVICE AND IS APPROVED FOR THIS TYPE OF | | | INSTALLATION OR CONSIDER THE USE OF ANOTHER LEAD FREE | | | DEVICE. THE UNIT CURRENTLY INSTALLED ON THE POOL | | | AUTOFILL MUST BE REPLACED. 2017 FBC-PLUMBING | | | SEC.605.2.1. | | | 3) SUBMIT TWO COPIES OF THE 975XL2 DEVICE AND TWO | | | COPIES OF THE DEVICE TO BE USED FOR THE POOL AUTOFILL | | | AND TWO COPIES OF THE DEVICE TO BE USED FOR THE | | | IRRIGATION SYSTEM. ALL DEVICES SHALL BE LEAD FREE. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|