Plan Review Notes
Plan Review Notes For Permit 18070221
Permit Number 18070221
Review Stop P
Sequence Number 2
Notes
Date Text
2018-07-26 08:01:081) THE SUBMITTED DOCUMENTS FOR THE RPZ DOES NOT STATE
 THAT THE DEVICE IS ON THE UNIVERSITY OF SOUTHERN
 CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL'S
 LIST OF APPROVED DEVICES. YOU NEED TO SUBMIT THE
 MANUFACTURER'S SPECIFICATIONS, NOT THE INSTALLATION
 INSTRUCTIONS. CITY OF WPB CROSS CONNECTION CONTROL
 MANUAL REQS.
 2) THE DESCRIPTION OF THE WORK ON THE PERMIT
 APPLICATION IS VAGUE. INDICATE ON THE PERMIT
 APPLICATION HOW MANY BACKFLOW DEVICES ARE BEING
 INSTALLED AND WHAT THEY ARE BEING INSTALLED ON (
 IRRIGATION, AUTOFILL FOR POOL, DOMESTIC SYSTEM?). WPB
 AMEND. TO FBC SEC. 107.2.1.
 3) THE MANFACTURER'S SPECIFICATIONS FOR THE ANTI-SIPHON
 PRESSURE VACUUM BREAKER CANNOT BE USED FOR BACKPRESSURE
 BACKFLOW PER THE MANUFACTURER'S SPECIFICATIONS AND THE
 SPECIFICATIONS DO NOT STATE THAT THE DEVICE IS LEAD
 FREE. SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS
 FOR THE CORRECT DEVICE TO BE USED FOR THE SPECIFIC
 APPLICATION. WPB AMEND. TO FBC SEC. 107.2.1.
 4) SUBMIT TWO COPIES OF A HAND DRAWN SITE PLAN SHOWIN
 THE LOCATION OF EACH DEVICE AND THE TYPE OF SYSTEM ON
 WHICH IT IS INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  