| Plan Review Notes For Permit 18070221 |
| Permit Number |
18070221 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-07-26 08:01:08 | 1) THE SUBMITTED DOCUMENTS FOR THE RPZ DOES NOT STATE | | | THAT THE DEVICE IS ON THE UNIVERSITY OF SOUTHERN | | | CALIFORNIA'S FOUNDATION FOR CROSS CONNECTION CONTROL'S | | | LIST OF APPROVED DEVICES. YOU NEED TO SUBMIT THE | | | MANUFACTURER'S SPECIFICATIONS, NOT THE INSTALLATION | | | INSTRUCTIONS. CITY OF WPB CROSS CONNECTION CONTROL | | | MANUAL REQS. | | | 2) THE DESCRIPTION OF THE WORK ON THE PERMIT | | | APPLICATION IS VAGUE. INDICATE ON THE PERMIT | | | APPLICATION HOW MANY BACKFLOW DEVICES ARE BEING | | | INSTALLED AND WHAT THEY ARE BEING INSTALLED ON ( | | | IRRIGATION, AUTOFILL FOR POOL, DOMESTIC SYSTEM?). WPB | | | AMEND. TO FBC SEC. 107.2.1. | | | 3) THE MANFACTURER'S SPECIFICATIONS FOR THE ANTI-SIPHON | | | PRESSURE VACUUM BREAKER CANNOT BE USED FOR BACKPRESSURE | | | BACKFLOW PER THE MANUFACTURER'S SPECIFICATIONS AND THE | | | SPECIFICATIONS DO NOT STATE THAT THE DEVICE IS LEAD | | | FREE. SUBMIT 2 COPIES OF MANUFACTURER'S SPECIFICATIONS | | | FOR THE CORRECT DEVICE TO BE USED FOR THE SPECIFIC | | | APPLICATION. WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) SUBMIT TWO COPIES OF A HAND DRAWN SITE PLAN SHOWIN | | | THE LOCATION OF EACH DEVICE AND THE TYPE OF SYSTEM ON | | | WHICH IT IS INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|