| Plan Review Notes For Permit 18070210 |
| Permit Number |
18070210 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-07-07 10:08:24 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | FBC 107. | | | | | | 1. PLEASE PROVIDE THE N.O.A. FOR THE MULLIONS TO BE | | | USED. | | | | | | NOTE: TYPICALLY IN THIS LOCATION, ATTACHING MULLIONS TO | | | KNEE WALLS BELOW THE WINDOWS, THE KNEE WALL STRUCTURE | | | IS NOT SUFFICIENT TO TRANSFER LOADS TO CONCRETE | | | STRUCTURE AS PER PRODUCT APPROVALS AND CODE | | | REQUIREMENTS. PLEASE CONSIDER SUBMITTING MULLIONS WITH | | | A LONGER LENGTH TO ATTACH DIRECTLY TO CONCRETE DECK | | | BELOW IF REQUIRED. | | | | | | 2. WORKERS COMP AND INSURANCE HAVE EXPIRED. PLEASE | | | UPDATE. |
|