| 2018-07-31 15:46:43 | PLAN REVIEW COMMENTS |
| | (COMMENTS FROM FIRST REVIEW WERE NOT ADDRESSED.) |
| | |
| | 2ND REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT GENERATOR PAD DRAWINGS WITH THE ENGINEER'S |
| | ORIGINAL HANDWRITTEN SIGNATURE. FAC 61G15-23.003 |
| | PROCEDURES FOR PHYSICALLY SIGNING AND SEALING PLANS, |
| | SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS. ENGINEERING |
| | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS WHICH |
| | MUST BE SIGNED, DATED AND SEALED IN ACCORDANCE WITH THE |
| | PROVISIONS OF SECTION 471.025, F.S., AND RULE |
| | 61G15-23.001, F.A.C. MUST BE PHYSICALLY SIGNED, DATED |
| | AND SEALED AS PROVIDED HEREIN BY THE PROFESSIONAL |
| | ENGINEER IN RESPONSIBLE CHARGE. |
| | (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE |
| | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE |
| | USED. |
| | (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY |
| | CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY |
| | OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE |
| | REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL |
| | NOT RENDER THE SIGNATURE ILLEGIBLE. |
| | |
| | 2) THE MODEL NUMBER (QT027) OF THE PROPOSED 27KW |
| | GENERATOR IS NOT LISTED ON THE GENERATOR PAD |
| | ENGINEERING THAT WAS SUBMITTED. THE GENERATOR PAD |
| | DRAWINGS NEED TO LIST THE GENERATOR MODEL THAT YOU WILL |
| | INSTALL. FBCR-G 2404.6 |
| | |
| | 3) THE ENGINEERED DRAWINGS THAT WERE SUBMITTED ARE FOR |
| | THE 2014 FBC (FIFTH EDITION) AND THE PROJECT IS UNDER |
| | THE 2017 FBC (SIXTH EDITION). SUBMIT TWO SETS OF |
| | UPDATED GENERATOR PAD DRAWINGS. |
| | |
| | |