2018-07-16 17:16:34PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) VALUATION OF $13,000.00 IS TOO LOW FOR THIS POOL.
 SUBMIT A COPY OF THE SIGNED CONTRACT. FBC 109.3
 BUILDING PERMIT VALUATION. FOR PERMITTING PURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT VALUE TO INCLUDE STRUCTURAL, ELECTRIC,
 PLUMBING, MECHANICAL, INTERIOR FINISH, RELATIVE SITE
 WORK, ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS,
 OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY
 INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT
 VALUATION SHALL BE SET BY THE BUILDING OFFICIAL.
  
 2) THE WATER DEPTH IN THIS PRIVATE POOL EXCEEDS 5 FEET.
 SHOW COMPLIANCE WITH FBC-R4501.18 LADDERS AND STEPS.
 ALL POOLS WHETHER PUBLIC OR PRIVATE SHALL BE PROVIDED
 WITH A LADDER OR STEPS IN THE SHALLOW END WHERE WATER
 DEPTH EXCEEDS 24 INCHES (610 MM). IN PRIVATE POOLS
 WHERE WATER DEPTH EXCEEDS 5 FEET (1524 MM), THERE SHALL
 BE LADDERS, STAIRS OR UNDERWATER BENCHES/SWIMOUTS IN
 THE DEEP END. WHERE MANUFACTURED DIVING EQUIPMENT IS TO
 BE USED, BENCHES OR SWIMOUTS SHALL BE RECESSED OR
 LOCATED IN A CORNER.
  
 3) NOTE: THE POOL PERMIT CAN NOT BE ISSUED WITHOUT A
 POOL ELECTRICAL SUB-PERMIT. SUBMIT AN APPLICATION FOR A
 POOL ELECTRICAL SUB-PERMIT.