| 2018-07-19 13:39:30 | |
| | 1) CITY RECORDS SHOW AN EXISTING GAS SYSTEM FOR THIS |
| | ADDRESS. THE EXISTING GAS DRAWING ON RECORD SHOWS A |
| | DEVELOPED LENGTH OF 60 FEET TO THE FARTHEST GAS OUTLET. |
| | THE SUBMITTED GAS PLAN SHOWS 15 FEET AS THE FARTHEST |
| | DISTANCE. CLARIFY. |
| | 2) THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE |
| | ADDED INTO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE |
| | THE EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, |
| | THE EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE |
| | OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM |
| | THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. THE |
| | EXISTING BTU LOAD SHOWN ON THE EXISTING GAS PLAN IS |
| | SHOWN AS 407,000 BTU'S. |
| | 3) THE SUBMITTED PLANS SHOW A 2 PSI SYSTEM AND THE |
| | ORIGINAL PLANS SHOW THE EXISTING SYSTEM AS LESS THAN 2 |
| | PSI. SHOW THE LOCATION OF ALL MP REGULATORS AND SHOW |
| | THE DISTANCE FROM THE OUTLET OF THE GAS METER TO THE |
| | FARTHEST MP REGULATOR ON THE SYSTEM. THIS DISTANCE |
| | SHALL BE USED FOR THE SIZING OF THE 2 PSI SYSTEM. |
| | 4) SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP |
| | REGULATORS TO FARTHEST OUTLET. THIS DISTANCE SHALL BE |
| | USED IN THE SIZING OF THE LOW PRESSUJRE SYSTEM. |
| | 5) SUBMIT PAGES 40 & 41 OF THE GAS REGULATOR SPECS. |
| | THESE ARE THE INSTALLATION INSSTRUCTIONS FOR THE |
| | REGULATORS. |
| | 6) THERE ARE TWO DIFFERENT SIZING TABLES FOR THE PE |
| | PIPE: ONE FROM NFPA 54 AND ONE FROM 2017 FBC-FUEL GAS. |
| | WHICH ONE IS BEING USED? REMOVE THE TABLE NOT BEING |
| | USED. |
| | 7) THE LOCATION OF THE GENERATOR EXHAUST EXHAUST SHALL |
| | COMPLY WITH THE MANUFACTURER'S INSTALLATION MANUAL OR |
| | IF NOT SPECIFIED IN THE MANUAL, A MINIMUM OF 10 FEET |
| | FROM ANY BUILDING OPENINGS. |
| | |
| | NOTE: FOR FUTURE GAS SUBMITTALS, ENSURE THERE ARE TWO |
| | COPIES OF EACH PAGE OF THE SPECIFICATIONS IN THE |
| | SUBMITTAL AND DIVIDED INTO TWO SEPARATE PACKETS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |