| 2018-09-21 17:40:04 | 09/21/2018 2ND GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE SECOND REQUEST, THE CITY RECORDS SHOW AN |
| | EXISTING GAS SYSTEM FOR THIS ADDRESS. THE EXISTING GAS |
| | DRAWING ON RECORD SHOWS A DEVELOPED LENGTH OF 60 FEET |
| | TO THE FARTHEST GAS OUTLET. THE SUBMITTED GAS PLAN |
| | SHOWS 15 FEET AS THE FARTHEST DISTANCE, PLEASE CLARIFY. |
| | SHOW ON THE GAS PLANS THE DISTANCE FROM THE MP |
| | REGULATORS TO THE FARTHEST OUTLET. THIS DISTANCE SHALL |
| | BE USED IN THE SIZING OF THE LOW-PRESSURE SYSTEM. |
| | |
| | 2. THE SECOND REQUEST, SUBMIT PAGES 40 & 41 OF THE GAS |
| | REGULATOR SPECS. THESE ARE THE INSTALLATION |
| | INSTRUCTIONS FOR THE REGULATORS. |
| | |
| | 3. THE SECOND REQUEST, THERE ARE TWO DIFFERENT SIZING |
| | TABLES FOR THE PE PIPE: ONE FROM NFPA 54 AND ONE FROM |
| | 2017 FBC-FUEL GAS. WHICH ONE IS BEING USED? REMOVE THE |
| | TABLE NOT BEING USED. |
| | |
| | 4. THE SECOND REQUEST, THE LOCATION OF THE GENERATOR |
| | EXHAUST SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION MANUAL OR IF NOT SPECIFIED IN THE MANUAL, |
| | A MINIMUM OF 10 FEET FROM ANY BUILDING OPENINGS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |