| Plan Review Notes For Permit 18070150 |
| Permit Number |
18070150 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-07 12:50:58 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET G 1 02 - THERE IS A NOTE BOX INDICATING THE | | | WORK IS ON THE 4TH FL COMMAND CENTER. | | | | | | FOR CLARIFICATION PURPOSES PLEASE INDICATE WHY THE ONLY | | | THE COMMAND CENTER IS INCLUDED. | | | | | | | | | | | | 2) SHEET G 1 02 - THERE IS AN INDICATION IN A NOTE BOX | | | THAT THE WORK ON THE 4TH FL COMMAND CENTER SHALL COMPLY | | | WITH THE 5TH ED OF THE FFPC. | | | | | | THE CURRENT ED OF THE FFPC IS THE 6TH. | | | | | | PLEASE REVIEW AND CORECT OR JUSTIFY WHY THE 5TH ED IS | | | INDICATED AND ALOS WHY THE NOT THE ENTIRE PROJECT. | | | | | | | | | | | | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|