| Notes |
| Date |
Text |
| 2019-01-28 13:21:52 | | | | MECHANICAL PROVISOS: | | | | | | A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL | | | PERMIT. | | | | | | B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION | | | SYSTEMS CONTROL. | | | | | | 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A. | | | | | | 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED: | | | | | | A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE | | | A CAPACITY GREATER THAN 2000 CFMS. | | | | | | B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS | | | SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY | | | GREATER THAN 2000 CFMS. | | | | | | C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES | | | THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS, | | | AT EACH STORY. | | | | | | D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL | | | LISTING AND MANUFACTURER'S SPECIFICATIONS. | | | |
|