2018-07-26 10:49:30 
 MECHANICAL PROVISOS:
  
 A) FL. LICENSED FIRE ALARM CONTRACTOR REQUIRED TO PULL
 PERMIT.
  
 B) SECTION 606 FBC-17 MECHANICAL, SMOKE DETECTION
 SYSTEMS CONTROL.
  
 1) DUCT SMOKE DETECTORS SHALL COMPLY WITH UL 268A.
  
 2) DUCT SMOKE DETECTORS SHALL BE INSTALLED:
  
 A) ON THE SUPPLY SIDE OF AIR HANDLING SYSTEMS THAT HAVE
 A CAPACITY GREATER THAN 2000 CFMS.
  
 B) ON THE SUPPLY SIDES OF MULTIPLE AIR-HANDLING SYSTEMS
 SHARING COMMON SUPPLY WITH A COMBINED DESIGN CAPACITY
 GREATER THAN 2000 CFMS.
  
 C) ON RETURN AIR RISERS SERVING TWO OR MORE STORIES
 THAT HAVE A DESIGN CAPACITY GREATER THAN 15,000 CFMS,
 AT EACH STORY.
  
 D) DEVICES SHALL BE TESTED IN ACCORDANCE WITH UL
 LISTING AND MANUFACTURER'S SPECIFICATIONS.
  
  
 CCOLE- 7/25/2018