2018-07-19 13:52:25THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET G 3 02 - THERE IS AN INDICATION OF COMPLIANCE
 WITH THE 5TH EDITION FOR THE FLORIDA FIRE PREVENTION
 CODE.
  
 THE CURRENT EDITION IS THE 6TH EDITION.
  
 PLEASE REVIEW, CORRECT, OR JUSTIFY AND ENSURE
 COMPLIANCE.
  
  
  
 2) SGEET G 3 02 - THE IS A REFERENCEUNDER THE LIFE
 SAFETY TABULAR BOX INDICATING WORK ON THE 4TH FLOOR
 COMMAND CENTER.
  
 THIS PLAN DOES NOT APPEAR TO ADDRESS THAT AREA AND IS
 CONFUSING.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 3) SHEET FA 1 01 - UNDER THE GENRAL SECTION THERE IS A
 REFERNCE TO THE 2011 EDITION OF THE NEC.
  
 THE CURRENT EDITION OF THE NFPA 70?, NATIONAL
 ELECTRICAL CODE?, 2014 EDITION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 4) FA 1 02 - UNDER PHASE VI THERE IS AN INDICATION OF
 APPLYING FIRE CAULK PER THE MANUFACTURES REQUIREMENTS.
 THIS IS AGENRAL STATEMENT THAT MAY NOT BE APPLICABLE.
  
 LIST FIRE RATED ASSEMBLIES SHALL BE SUBMITTED FOR
 REVIEW AND APPROVAL.
  
 PROVIDE DETAILS OF LISTED FIRE RATED ASSEMBLIES FOR THE
 OPENINGS OR PROVIDE AN APPLICABLE NOTE TO PROVIDE
 LISTED ASSEMBLIES FOR REVIEW AND APPROVAL PRIOR TO ANY
 INSPECTION.
  
  
  
 5) SHEET FA 2 01 - STAFF BREAKROOM A1A19, DOES NOT
 INDICATE A NOTIFICATION DEVICE.
  
 SHOULD THE EXISTING CONDITION NOT HAVE A DEVICE, ONE IS
 REQUIRED IN THE SPACE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
  
 6) SHEET FA 2 01 - WOMENS RESTROOM A1A10 & MENS
 RESTROOM A1A12, INDICATE ONLY 75CD WITH NO DEVICE
  
 PLEASE REVIEW AND INDICATE WHAT DEVICE IS LOCATED IN
 THESE AREAS.
  
  
  
 7) ALL FA SHEETS - THERE ARE ADDRESSABLE INDICATORS ON
 ANY DEVICE ON ANY SHEET DRAWINGS.
  
 ALL DEVICES SHALL BE ADDRESSABLE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 8) FA 3 02 - THE FIRE ALARM RISER DOES NOT HAVE ANY
 ADDRESSABLE INDICATORS ON ANY DEVICE.
  
 ALL DEVICES SHALL BE ADDRESSABLE.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  