| 2018-07-18 15:44:00 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) SHEET GEN 2.1 - THERE IS AN INDICATION IN THE DATA |
| | TABULAR BOX OF FFPC 5TH EDITION. |
| | |
| | THE CURENT EDITION OF THE FFPC IS THE 6TH EDITION. |
| | |
| | PLEASE CORRECT AND ENSURE COMPLIANCE AND/OR JUSTIFY |
| | WITH SPECIFIC DETAIL. |
| | |
| | |
| | |
| | 2) SHEET LS 100 - THE CORRIDOR/SPACE BETWEEN THE PUBLIC |
| | LOBBY AND ELEVATOR LOBBY IS INDICATED AS BEING |
| | NARROWED; HOWEVER, THERE ARE NO DIMENSIONS INDICATED. |
| | |
| | WHAT IS THE REQUIRED DIMENSION FOR THE EXIT PATHWAY AND |
| | PROVIDE THAT DIMENSION TO THIS AREA. |
| | |
| | |
| | |
| | |
| | 3) SHEET FP 1.04.1 - STATEMENT # 3 INDICATES STATE FIRE |
| | MARSHAL APPROVAL PRIOR TO ANY INSTALLATION. |
| | |
| | IS THIS A STRICT CONDITION TO BE BE ENFORCED? |
| | |
| | HAS APPROVAL BEEN GRANTED? PROVIDE APPLICABLE DETAILS. |
| | |
| | |
| | |
| | |
| | 4) SHEET FP 1.04.1 - PROVIDE A NOTE INDICATING THAT THE |
| | FIRE SPRINKLER SHALL REMAIN FULLY OPERATIONAL DURING |
| | ALL CONSTRUCTION. |
| | |
| | |
| | |
| | |
| | 5) SHEET FAC 1.04.1 - PROVIDE A NOTE INDICATING THAT |
| | THE FIRE ALARM SHALL REMAIN FULLY OPERATIONAL DURING |
| | ALL CONSTRUCTION. |
| | |
| | |
| | |
| | |
| | 6) SHEET FAC 1.01 - THERE IS AN INDICATION IN THE |
| | GENERAL SECTION OF NOTE # 1 STATING COMPLIANCE WITH NEC |
| | 2011. |
| | |
| | PER THE FLORIDA FIRE PREVENTION CODE 6TH EDITION, |
| | COMPLIANCE SHALL BE WITH NFPA 70?, NATIONAL ELECTRICAL |
| | CODE?, 2014 EDITION. |
| | |
| | PLEASE CORRECT OR JUSTIFY. |
| | |
| | |
| | |
| | |
| | 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |