2018-07-18 15:44:00THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET GEN 2.1 - THERE IS AN INDICATION IN THE DATA
 TABULAR BOX OF FFPC 5TH EDITION.
  
 THE CURENT EDITION OF THE FFPC IS THE 6TH EDITION.
  
 PLEASE CORRECT AND ENSURE COMPLIANCE AND/OR JUSTIFY
 WITH SPECIFIC DETAIL.
  
  
  
 2) SHEET LS 100 - THE CORRIDOR/SPACE BETWEEN THE PUBLIC
 LOBBY AND ELEVATOR LOBBY IS INDICATED AS BEING
 NARROWED; HOWEVER, THERE ARE NO DIMENSIONS INDICATED.
  
 WHAT IS THE REQUIRED DIMENSION FOR THE EXIT PATHWAY AND
 PROVIDE THAT DIMENSION TO THIS AREA.
  
  
  
  
 3) SHEET FP 1.04.1 - STATEMENT # 3 INDICATES STATE FIRE
 MARSHAL APPROVAL PRIOR TO ANY INSTALLATION.
  
 IS THIS A STRICT CONDITION TO BE BE ENFORCED?
  
 HAS APPROVAL BEEN GRANTED? PROVIDE APPLICABLE DETAILS.
  
  
  
  
 4) SHEET FP 1.04.1 - PROVIDE A NOTE INDICATING THAT THE
 FIRE SPRINKLER SHALL REMAIN FULLY OPERATIONAL DURING
 ALL CONSTRUCTION.
  
  
  
  
 5) SHEET FAC 1.04.1 - PROVIDE A NOTE INDICATING THAT
 THE FIRE ALARM SHALL REMAIN FULLY OPERATIONAL DURING
 ALL CONSTRUCTION.
  
  
  
  
 6) SHEET FAC 1.01 - THERE IS AN INDICATION IN THE
 GENERAL SECTION OF NOTE # 1 STATING COMPLIANCE WITH NEC
 2011.
  
 PER THE FLORIDA FIRE PREVENTION CODE 6TH EDITION,
 COMPLIANCE SHALL BE WITH NFPA 70?, NATIONAL ELECTRICAL
 CODE?, 2014 EDITION.
  
 PLEASE CORRECT OR JUSTIFY.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL