| 2018-07-30 14:47:04 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. AS THIS PLAN IS A SUBMISSION FOR THE FIRE ALARM |
| | SYSTEM, THE PLAN SUBMITTED SHOULD CONTAIN JUST THE FIRE |
| | ALARM SYSTEM AND ANY ELECTRICAL TO FEED THAT SYSTEM. |
| | REMOVE ALL LIGHTING, POWER, AND LOW VOLTAGE SYSTEMS NOT |
| | PART OF FIRE ALARM INSTALLATION. WPB FBC 107.2.1 |
| | 2. PLAN REVIEW STAFF WAS ADVISED THAT THIS WAS A |
| | MULTI-MILLION DOLLAR JOB. VALUE FOR WORK STATED ON |
| | PERMIT APPLICATION APPEARS LOW. PROVIDE COPY OF SIGNED |
| | CONTRACT WITH SCOPE AND VALUE OF WORK, TO INCLUDE ALL |
| | MATERIALS AND LABOR. DETAIL HOW THIS COST WILL BE SPLIT |
| | BETWEEN THE RESPECTIVE PERMITS. FBC 109.3 |
| | 3. THE NEC AND FBC SPECIFIED FOR DESIGN ON SHEET G2.01 |
| | IS NOT THE CURRENT CODE. PROVIDE CORRECTION. FBC |
| | PREFACE (ALSO SEE CURRENT CODES ABOVE) |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |