| 2018-07-09 06:33:26 | 1) INDICATE THE TYPE OF PIPE TO BE INSTALLED. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 2) THE GAS PLAN SHOWS THE GAS PIPE SIZE AS 3/4 INCH AND |
| | ALSO AS 1/2 INCH IN SIZE. CLARIFY. |
| | 3) CITY RECORDS SHOW AN EXISTING GAS RANGE AND ALSO A |
| | WATER HEATER ON THE GAS SYSTEM WITH A GAS . THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | 4) THE EXISTING GAS SYSTEM AND THE SUBMITTED GAS PLAN |
| | WAS SIZED ON A 0.5 INCH WATER COLUMN BUT THE SIZING |
| | TABLE THAT IS REFERENCED ON THE SUBMITTED PLAN IS FOR A |
| | 6.0 INCH WATER COLUMN PRESSURE DROP. CLARIFY. |
| | 5) THE SUBMITTED GAS PLAN REFERENCES NFPA 54 TABLE 612 |
| | (D). THERE IS NO SUCH TABLEE IN NFPA 54. CLARIFY. |
| | 6) SUBMIT A HAND DRAWN FLOOR PLAN SHOWING THE LOCATION |
| | OF THE BBQ GRILL. IF THE GRILL IS LOCATED UNDER A |
| | ROOFEED STRUCTURE, A HOOD WILL BE REQUIRED OVER THE BBQ |
| | GRILL. |
| | |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |