2018-09-02 15:55:05CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR FOR
 ENTIRE PROJECT. FBC 109.3 (CONTRACT PROVIDED DOES
 INCLUDE ALL WORK. PROVIDE TOTAL BREAKSOWN WITH ALL
 TRADES SHOWN. THIS MUST INCLUDE VALUE OF MATERIALS
 WHETHER THE CONTRACTOR SUPPLIES THEM OR THE OWNER
 PROVIDES.)
 2. ELECTRICAL NOTE STATES: "ALL WP OUTLETS SHALL BE
 WITH GFCI PROTECTION PER N.E.C.8.(B).3". THIS CODE
 SECTION DOES NOT EXIST. PROVIDE CORRECTION. NEC 210.8;
 WPB FBC 107.2.1 (NOTE STILL STATES WRONG CODE SECTION,
 AND THEN STATES PROPER CODE ARTICLE. CORRECT
 DISCREPANCY.)
 3. OTHER ELECTRICAL NOTE STATES: "PROSSIGERS ROOM IN
 MEDICAL FACILITIES AS PER 517.13 FBC 2017 6TH ED." THIS
 CODE SECTION DOES NOT EXIST IN THE FBC. DOES THIS NOTE
 RELATE TO PATIENT CARE AREAS AND THE REDUNDANT
 GROUNDING REQUIREMENTS OF NEC 517.13? PROVIDE
 CLARIFICAITON AND/OR CORRECTION. DO YOU MEAN PROCEDURE
 ROOMS? NOTE SHOULD CLEARLY REFLECT WHAT THE NEC STATES
 FOR THE REQUIREMENT. IDENTIFY THESE ROOMS ON PLAN. WPB
 FBC 107.2.1 (NOT CORRECTED. ROOMS NOT IDENTIFIED.)
 4. ELECTRICAL MAINS NEED TO BE GROUPED PER NEC 230.72.
 (AS THESE MAINS ARE EXISTING, PROVIDE SIGNAGE DETAILS
 TO IDENTIFY ALL MAIN LOACATIONS PER NEC 230.2(E) )
 5. IT APPEARS FROM THE RISER DIAGRAM AND PANEL
 SCHEDULES THAT THERE IS NOT A MAIN DISCONNECT FOR EACH.
 AN UNGROUNDED CONDUCTOR IS NOT PERMITTED TO ENTER A
 BUIDLING WITHOUT OVERCURRENT AND DISCONNECTING MEANS,
 GREATER THAN 8 FEET. PROVIDE CORRECTION. NEC 230.70
 (RISER DIAGRAM WAS REMOVED FROM PLAN. PROVIDE RISER
 DETAIL, SHOWING ALL ASPECTS OF EXISTING SERVICE. NEC
 215.5)
 6. CORRECTED, EXISTING SERVICE AND PANELS.
 7. CORRECTED, EXISTING SERVICE AND PANELS.
 8. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES
 EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN
 RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR
 LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2
 (NOT PROVIDED.)
 9. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS
 STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT
 SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 (NOT
 PROVIDED.)
 10. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS PER NEC
 210.62. (DO NOT KNOW IF COMPLIED OR NOT BECAUSE PANEL
 SCHEDULES WERE REMOVED FROM PLAN.)
 11. CORRECTED.
 12. CORRECTED.
 13. CORRECTED.
 14. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND
 FOR EACH PANEL. DEMAND FACTORS PERMITTED IN RESIDENTIAL
 INSTALLATIONS ARE NOT PERMITTED FOR COMMERCIAL
 INSTALLATIONS. NEC 220 (NOT PROVIDED.)
  
 NEW COMMENTS:
  
 15. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR
 ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE
 CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE APPLICABLE
 TO COMPLY WITH CODE. NEC 210.8, 210.12, 210.19, 210.20,
 215.5, 408.4
 16. PLEASE BE ADVISED THAT SOME OF THESE COMMENTS HAVE
 NOT BEEN ADDRESSED FOR TWO REVIEWS. IF UPON THE THIRD
 REVIEW, IF IT IS NECESSARY TO REJECT THE SUBMITTED PLAN
 A THIRD TIME FOR THE SAME REASONS, AN ADDITIONAL PLAN
 REVIEW IS REQUIRED. FLORIDA STATUTES STATE: WITH
 RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW. FS 553.80(2)(B)
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  