| 2018-08-09 14:20:16 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. 5 OF 11 WHY IS THERE 3 DIFFERENT HANDICAP |
| | BATHROOM DETAILS I FOUND THE FOLLOWING CODE VIOLATIONS. |
| | A) THE BOTTOM 2 DETAILS SHOW THE TOILET SEAT AT 15" IT |
| | SHALL BE 17"- 19" PLEASE CLARIFY PER FBC ACC 604.4 |
| | B) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE FROM FINISHED FLOOR AT 33"-36" PER FBC |
| | ACC 609.4 |
| | C) THE DETAIL ON THE TOP OF THE PAGE FOR THE LAVATORY |
| | SHOWS THE TOP OF THE RIM AT 35" IT SHALL BE 34" PER FBC |
| | ACC 606.3 |
| | D THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG |
| | MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER |
| | CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES |
| | MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2 |
| | |
| | 2. SHOW THE LOCATIONOF THE NEW WATER HEATER SHOWN ON |
| | SHT. 7 OF 11. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. IS THE WATER HEATER REPACLING AN EXITING ONE OR IS |
| | IT A NEW INSTALLATION IF IT IS A NEW INSTALLATION IT |
| | SHALL COMPLY WITH FBC PL 416.5 TEMPERED WATER SHALL BE |
| | DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES |
| | LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR |
| | CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL |
| | BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE |
| | LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA |
| | B125.3. |
| | |
| | 4. SHT. 2 OF 11 HAS DETAIL FOR A SLAB REPAIR IS THERE |
| | NEW PLUMBING PIPES BEING INSTALLED PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. 7 OF 11 HAS SEVERAL NOTES, TABLES AND DETAILS |
| | REFERENCING SEVERAL DIFFERENT PLUMBING FIXTURES AND |
| | PIPING THAT ARE NOT ON THE FLOOR PLAN AND NOT SHOWN ON |
| | THE SCOPE OF WORK IT IS UNCLEAR OF WHAT PLUMBING WORK |
| | IS BEING DONE PLEASE PROVIDE A DETAIL SCOPE OF PLUMBING |
| | WORK THAT IS BEING DONE AND PROVIDE PIPING ISOMETRICS |
| | FOR NEW PIPING. PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |