Plan Review Notes
Plan Review Notes For Permit 18070139
Permit Number 18070139
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-09 14:20:161ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. 5 OF 11 WHY IS THERE 3 DIFFERENT HANDICAP
 BATHROOM DETAILS I FOUND THE FOLLOWING CODE VIOLATIONS.
 A) THE BOTTOM 2 DETAILS SHOW THE TOILET SEAT AT 15" IT
 SHALL BE 17"- 19" PLEASE CLARIFY PER FBC ACC 604.4
 B) THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR AT 33"-36" PER FBC
 ACC 609.4
 C) THE DETAIL ON THE TOP OF THE PAGE FOR THE LAVATORY
 SHOWS THE TOP OF THE RIM AT 35" IT SHALL BE 34" PER FBC
 ACC 606.3
 D THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE. PER FBC ACC 604.5.2
  
 2. SHOW THE LOCATIONOF THE NEW WATER HEATER SHOWN ON
 SHT. 7 OF 11. PER WPB AMEND TO FBC 107.2.1
  
 3. IS THE WATER HEATER REPACLING AN EXITING ONE OR IS
 IT A NEW INSTALLATION IF IT IS A NEW INSTALLATION IT
 SHALL COMPLY WITH FBC PL 416.5 TEMPERED WATER SHALL BE
 DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
  
 4. SHT. 2 OF 11 HAS DETAIL FOR A SLAB REPAIR IS THERE
 NEW PLUMBING PIPES BEING INSTALLED PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 5. SHT. 7 OF 11 HAS SEVERAL NOTES, TABLES AND DETAILS
 REFERENCING SEVERAL DIFFERENT PLUMBING FIXTURES AND
 PIPING THAT ARE NOT ON THE FLOOR PLAN AND NOT SHOWN ON
 THE SCOPE OF WORK IT IS UNCLEAR OF WHAT PLUMBING WORK
 IS BEING DONE PLEASE PROVIDE A DETAIL SCOPE OF PLUMBING
 WORK THAT IS BEING DONE AND PROVIDE PIPING ISOMETRICS
 FOR NEW PIPING. PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  