Plan Review Notes
Plan Review Notes For Permit 18070139
Permit Number 18070139
Review Stop M
Sequence Number 1
Notes
Date Text
2018-07-16 17:45:461ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18070139
 7/16/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO SECTION 809.2 FBC-17 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3.1.1. FBC-17
 MECHANICAL. PROVIDE A SCHEDULE THAT INDICATES THE
 REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR.
  
 2) NO RETURN AIR SYSTEM IS SHOWN ON THE PLANS, PLEASE
 PROVIDE A MEANS OF RETURN AIOR FROM THE ROOMS AND
 SPACES BACK TO THE AIR HANDLER- SECTION 601.6 FBC M.
  
 3) THE PROPOSED PROJECT IS CLASSIFIED AS A "CHANGE OF
 OCCUPANCY" AS DEFINED IN SECTION 202 FBC EX. PLEASE
 SUBMIT A COMPLETE ENERGY COMPLIANCE REPORT AS REQUIRED
 BY SECTION C505.1 FBC EC. THE CURRENT SUBMITTALS IS
 LACKING THE COVER SHEET, CERTIFICATIONS PAGE,
 COMPLIANCE REPORT, AND CHECKLISTS- SEE SECTION C101.5.1
 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  