| 2018-07-30 12:53:02 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| | LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| | VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR FOR |
| | ENTIRE PROJECT. FBC 109.3 |
| | 2. ELECTRICAL NOTE STATES: "ALL WP OUTLETS SHALL BE |
| | WITH GFCI PROTECTION PER N.E.C.8.(B).3". THIS CODE |
| | SECTION DOES NOT EXIST. PROVIDE CORRECTION. NEC 210.8; |
| | WPB FBC 107.2.1 |
| | 3. OTHER ELECTRICAL NOTE STATES: "PROSSIGERS ROOM IN |
| | MEDICAL FACILITIES AS PER 517.13 FBC 2017 6TH ED." THIS |
| | CODE SECTION DOES NOT EXIST IN THE FBC. DOES THIS NOTE |
| | RELATE TO PATIENT CARE AREAS AND THE REDUNDANT |
| | GROUNDING REQUIREMENTS OF NEC 517.13? PROVIDE |
| | CLARIFICAITON AND/OR CORRECTION. DO YOU MEAN PROCEDURE |
| | ROOMS? NOTE SHOULD CLEARLY REFLECT WHAT THE NEC STATES |
| | FOR THE REQUIREMENT. IDENTIFY THESE ROOMS ON PLAN. WPB |
| | FBC 107.2.1 |
| | 4. ELECTRICAL MAINS NEED TO BE GROUPED PER NEC 230.72. |
| | 5. IT APPEARS FROM THE RISER DIAGRAM AND PANEL |
| | SCHEDULES THAT THERE IS NOT A MAIN DISCONNECT FOR EACH. |
| | AN UNGROUNDED CONDUCTOR IS NOT PERMITTED TO ENTER A |
| | BUIDLING WITHOUT OVERCURRENT AND DISCONNECTING MEANS, |
| | GREATER THAN 8 FEET. PROVIDE CORRECTION. NEC 230.70 |
| | 6. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10 |
| | 7. PROVIDE AIC RATING OF SERVICE DISCONNECT AND PANEL. |
| | NEC 110.3, 110.9 |
| | 8. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| | EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| | RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| | LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| | 9. PROVIDE THE ADDITIONAL INTERIOR LIGHTING CONTROLS |
| | STIPULATED IN THE FBC ENERGY CODE. MANY AREAS DO NOT |
| | SHOW THE AUTOMATIC CONTROL REQUIRED. FBC EC C405.2 |
| | 10. PROVIDE SHOW WINDOW RECEPTACLE OUTLETS PER NEC |
| | 210.62. |
| | 11. PROVIDE GFCI PROTECTED OUTLET FOR SERVICING OF A/C |
| | EQUIPMENT WITHIN 25 FEET OF THE EQUIPMENT PER CODE. NEC |
| | 210.63 |
| | 12. PROVIDE THE REQUIRED SERVICE AREA RECEPTACLE PER |
| | CODE. NEC 210.64 |
| | 13. PROVIDE DEDICATED CIRCUIT AND CONTROL FOR SIGN. NEC |
| | 600.5; FBC EC 405.2.4 |
| | 14. PROVIDE ACCURATE LOAD CALCULATION FOR SERVICE AND |
| | FOR EACH PANEL. DEMAND FACTORS PERMITTED IN RESIDENTIAL |
| | INSTALLATIONS ARE NOT PERMITTED FOR COMMERCIAL |
| | INSTALLATIONS. NEC 220 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |
| | SINCERELY, |
| | |
| | JOHN PEARSON |
| | ELECTRICAL PLANS EXAMINER |
| | 561-805-6746 |
| | [email protected] |
| | |