Plan Review Notes
Plan Review Notes For Permit 18070084
Permit Number 18070084
Review Stop P
Sequence Number 2
Notes
Date Text
2018-12-13 13:33:102ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS PLEASE
 PROVIDE DETAILS WITH HEIGHT AND LOCATION DIMENSIONS.
 PER FHA REQUIREMENT #6
  
 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION
 GUIDE FOR THE KEMPER SYSTEM USED IN THE SHOWER PANS.
 PER WPB AMEND TO FBC 107.2.1
  
 3. FLOOR DRAINS AND OR HUB DRAINS SHALL BE INSTALLED
 ACCESSIBLE LOCATION THE WALL CHASE THAT IT IS SHOWN IN
 IS A CODE VIOLATION. PER FBC PL 412.2
  
 4. THE STEAM GENERATOR SHALL BE INSTALLED ACCESSIBLE
 LOCATION THE WALL CHASE THAT IT IS SHOWN IN IS A CODE
 VIOLATION. PER FBC PL 502.5
  
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  