| 2018-12-13 13:33:10 | 2ND REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. GRAB BAR BACKING IS REQUIRED IN ALL BATHROOMS PLEASE |
| | PROVIDE DETAILS WITH HEIGHT AND LOCATION DIMENSIONS. |
| | PER FHA REQUIREMENT #6 |
| | |
| | 2. PROVIDE MANUFACTURE SPECIFICATION AND INSTILLATION |
| | GUIDE FOR THE KEMPER SYSTEM USED IN THE SHOWER PANS. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. FLOOR DRAINS AND OR HUB DRAINS SHALL BE INSTALLED |
| | ACCESSIBLE LOCATION THE WALL CHASE THAT IT IS SHOWN IN |
| | IS A CODE VIOLATION. PER FBC PL 412.2 |
| | |
| | 4. THE STEAM GENERATOR SHALL BE INSTALLED ACCESSIBLE |
| | LOCATION THE WALL CHASE THAT IT IS SHOWN IN IS A CODE |
| | VIOLATION. PER FBC PL 502.5 |
| | |
| | |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |