Plan Review Notes
Plan Review Notes For Permit 18070084
Permit Number 18070084
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-17 14:02:311ST REVIEW FBC-2010 FLORIDA BUILDING CODES- MECHANICAL
 PERMIT #18070084
 9/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION CODE
 FBC FG- FLORIDA FUEL GAS CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE COMCHECK COMPLIANCE CERTIFICATE LISTS COOLING
 AND HEATING CAPACITIES AND EFFICENCY RATINGS FOR THE AC
 SYSTEMS THAT DO NOT MATCH THE DATA SHOWN IN THE AC
 EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB. PLEASE NOTE
 THE PLANS ARE BEING REVIEWED UNDER THE 2010 CODES,
 HOWEVER THE COMCHECK SUBMITTAL IS THE 2017 VERSION.
  
 2) SUBMIT AC CALCULATIONS FOR THE NEW MINI SPLIT
 SYSTEM- 503.2.1 FBC- EC., AND PROVIDE COMPLIANCE DATA
 FOR THE SYSTEM IN THE REVISED COMCHECK CERTIFICATE.
  
 3) SHEET M-1.0: VERIFY THAT THE DRYER AND KITCHEN
 EXHAUST DUCTS ARE NOT RUNNING THROUGH THE ABOVE-
 CEILING PLENUM- SECTIONS 504.4 & 601.5 FBC M.
  
 4) M-1.0: SMOKE DETECTORS ARE REQUIRED IN BOTH THE
 SUPPLY AND RETURN AIR SYSTEMS OF THE HEAT PUMPS IN
 ACCORDANCE WITH SECTION 606.2.2 FBC M.
  
 5) SUBMIT CUT SHEETS AND PROVIDE EQUIPMENT SCHEDULES ON
 THE PLANS FOR THE KITCHEN COOKING APPLIANCES- SECTION
 623 FBC FG,.
  
 6) SUBMIT CUT SHEETS FOR THE KITCHEN EXHAUST HOOD AND
 EXHAUST DUCT. INDICATE HOW MAKEUP AIR IS BEING PROVIDED
 FOR THE EXHAUST AND PROVIDE EXHAUST AND AIR BALANCE
 CALCULATIONS- SECTIONS 505, 506, 507, & 508 FBC M.
 PLEASE NOTE THAT A FIRE SUPPRESSION SYSTEM MAY BE
 REQUIRED PER SECTION 509.1 FBC M.
  
 7) SUBMIT CUT SHEETS FOR THE DRYERS AND INDICATE HOW
 MAKE UP AIR IS BEING PROVIDED- SECTION 504.5 FBC M.
  
 8) M-1.0 & M-2.10: PROVIDE A DETAIL SHOWING HOW THE
 FIRE DAMPERS WILL BE INSTALLED IN THE DUCTS CONNECTING
 TO THE RISERS. PLEASE SUBMIT SPECS FOR THE DAMPERS WITH
 AN APPROVAL STAMP BY THE EOR.
  
 9) M-1.0: THE TOILET EXHAUST RISER BY POWDER RM 118 IS
 MISLABELED AS KER-2.
  
 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE
 MINI-SPLIT AIR HANDLER AT THE BAR- SECTION 307 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  