| 2018-09-17 14:02:31 | 1ST REVIEW FBC-2010 FLORIDA BUILDING CODES- MECHANICAL |
| | PERMIT #18070084 |
| | 9/17/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE |
| | FBC M- FLORIDA MECHANICAL CODE |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE |
| | FBC FG- FLORIDA FUEL GAS CODE |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2010 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE COMCHECK COMPLIANCE CERTIFICATE LISTS COOLING |
| | AND HEATING CAPACITIES AND EFFICENCY RATINGS FOR THE AC |
| | SYSTEMS THAT DO NOT MATCH THE DATA SHOWN IN THE AC |
| | EQUIPMENT SCHEDULE- SECTION 107.2.1 WPB. PLEASE NOTE |
| | THE PLANS ARE BEING REVIEWED UNDER THE 2010 CODES, |
| | HOWEVER THE COMCHECK SUBMITTAL IS THE 2017 VERSION. |
| | |
| | 2) SUBMIT AC CALCULATIONS FOR THE NEW MINI SPLIT |
| | SYSTEM- 503.2.1 FBC- EC., AND PROVIDE COMPLIANCE DATA |
| | FOR THE SYSTEM IN THE REVISED COMCHECK CERTIFICATE. |
| | |
| | 3) SHEET M-1.0: VERIFY THAT THE DRYER AND KITCHEN |
| | EXHAUST DUCTS ARE NOT RUNNING THROUGH THE ABOVE- |
| | CEILING PLENUM- SECTIONS 504.4 & 601.5 FBC M. |
| | |
| | 4) M-1.0: SMOKE DETECTORS ARE REQUIRED IN BOTH THE |
| | SUPPLY AND RETURN AIR SYSTEMS OF THE HEAT PUMPS IN |
| | ACCORDANCE WITH SECTION 606.2.2 FBC M. |
| | |
| | 5) SUBMIT CUT SHEETS AND PROVIDE EQUIPMENT SCHEDULES ON |
| | THE PLANS FOR THE KITCHEN COOKING APPLIANCES- SECTION |
| | 623 FBC FG,. |
| | |
| | 6) SUBMIT CUT SHEETS FOR THE KITCHEN EXHAUST HOOD AND |
| | EXHAUST DUCT. INDICATE HOW MAKEUP AIR IS BEING PROVIDED |
| | FOR THE EXHAUST AND PROVIDE EXHAUST AND AIR BALANCE |
| | CALCULATIONS- SECTIONS 505, 506, 507, & 508 FBC M. |
| | PLEASE NOTE THAT A FIRE SUPPRESSION SYSTEM MAY BE |
| | REQUIRED PER SECTION 509.1 FBC M. |
| | |
| | 7) SUBMIT CUT SHEETS FOR THE DRYERS AND INDICATE HOW |
| | MAKE UP AIR IS BEING PROVIDED- SECTION 504.5 FBC M. |
| | |
| | 8) M-1.0 & M-2.10: PROVIDE A DETAIL SHOWING HOW THE |
| | FIRE DAMPERS WILL BE INSTALLED IN THE DUCTS CONNECTING |
| | TO THE RISERS. PLEASE SUBMIT SPECS FOR THE DAMPERS WITH |
| | AN APPROVAL STAMP BY THE EOR. |
| | |
| | 9) M-1.0: THE TOILET EXHAUST RISER BY POWDER RM 118 IS |
| | MISLABELED AS KER-2. |
| | |
| | 10) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE |
| | MINI-SPLIT AIR HANDLER AT THE BAR- SECTION 307 FBC M. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |