Plan Review Notes
Plan Review Notes For Permit 18070084
Permit Number 18070084
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-17 08:17:55CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. AFCI PROTECTION SHOWN IN NOT CODE COMPLIANT. ALL
 BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15-
 AND 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY
 ROOMS, DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES,
 DENS, BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. THIS INCLUDES LIGHTING AND
 POWER OUTLETS AND RECEPTACLES. SOME AREAS REQUIRE BOTH
 AFCI AND GFCI PROTECTION. PROVIDE CORRECTION. NEC
 210.8, 210.12
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC 210.8(D)
 3. NOTE 3 INDICATES THERE ARE OUTLETS ON BUNK BED.
 PROVIDE SPEC SHEET TO CONFIRM LISTING. NEC 110.3
 4. NOTE 5 INDICATES A REGULAR RECEPTACLE OUTLET
 INSTALLED IN MEDICINE CABINET., AND NOTE 6 INDICATES
 RECEPTACLE OUTLETS INSIDE VANITY DRAWERS. ALL
 RECEPTACLE OUTLETS INSTALLED IN A BATHROOM REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8
 5. PLAN SHOWS LED LIGHTING WITHIN THE STORAGE SPACE OF
 THE CLOSET. PROVIDE LISTING OF PRODUCT TO CONFIRM IT IS
 LISTED FOR THIS USE. NEC 410.16, 110.3
 6. PROVIDE SPEC SHEET FOR TOWEL HEATER. NEC 110.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "OLD
 SHEETS".
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved