2018-07-23 12:21:371) SHT. 4 OF 4 - SEVERAL OF THE NOTES REFER TO THE 2006
 EDITION OF APSP-7. THE 2013 EDITION IS IN EFFECT, NOT
 THE 2006. REVISE NOTES # 7 & 8.
 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM
 ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN
 DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC
 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION
 ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT
 REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED
 THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET
 FITTING ASSEMBLY (DRAIN COVER).THE TDH CALCULATIONS
 MUST INCLUDE ALL OF THE SYSTEM COMPONENTS IN THE PIPING
 SYSTEM INCLUDING THE FILTER.
 3) SUBMIT TWO COPIES OF THE POOL PUMP CURVE. IDENTIFY
 ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC TO THE
 PUMP BEING INSTALLED ON THIS POOL. THIS IS NEEDED TO
 CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH
 CALCULATIONS.
 4) INDICATE ON THE POOL PUMP SPECS WHICH PUMP IS BEING
 INSTALLED. WPB AMEND. TO FBC SEC. 107.2.1.
  
 5) SUBMIT AN EXPANDED POOL PUMP CURVE. THE ONE ON SHEET
 2 OF 4 IS BARELY LEGIBLE. WPB AMEND. TO FBC SEC.
 107.2.1.
 6) SUBMIT TWO COPIES OF THE MANUF. SPECS FOR THE MAIN
 DRAIN.WPB AMEND. TO FBC SEC. 107.2.1.
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692