| 2018-07-25 16:30:23 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070082 |
| | 7/25/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | THE FOLLOWING COMMENTS ARE ADDRESSING THE MECHANICAL |
| | PLANS THAT WERE DESIGNED BY FELIX MENDEZ P.E. OF 3FM |
| | CONSULTING ENGINEERS. PLEASE NOTE THERE IS A SEPARATE |
| | SET OF MECHANICAL PLANS DESIGNED BY ROBERT L. QUETHEM |
| | P.E. THAT WERE APPROVED UNDER PERMIT #18051434. THERE |
| | CANNOT BE TWO ENGINEERS OF RECORD FOR THE PROPOSED |
| | PROJECT PER FLORIDA STATUTE 471. |
| | |
| | 1) SHEET M101: DUCT SMOKE DETECTORS ARE REQUIRED FOR |
| | EACH OF THE RTU'S IN ACCORDANCE WITH SECTION 606.2.1 |
| | FBC- M. PLEASE SHOW THE LOCATIONS OF THE REQUIRED |
| | DEVICES AND INDICATE COMPLIANCE WITH THE FOLLOWING CODE |
| | SECTIONS: |
| | |
| | 606.4 CONTROLS OPERATION. |
| | UPON ACTIVATION, THE SMOKE DETECTORS SHALL SHUT DOWN |
| | ALL OPERATIONAL CAPABILITIES OF THE AIR DISTRIBUTION |
| | SYSTEM IN ACCORDANCE WITH THE LISTING AND LABELING OF |
| | APPLIANCES USED IN THE SYSTEM. AIR DISTRIBUTION SYSTEMS |
| | THAT ARE PART OF A SMOKE CONTROL SYSTEM SHALL SWITCH TO |
| | THE SMOKE CONTROL MODE UPON ACTIVATION OF A DETECTOR. |
| | |
| | 606.4.1 SUPERVISION. |
| | THE DUCT SMOKE DETECTORS SHALL BE CONNECTED TO A FIRE |
| | ALARM SYSTEM WHERE A FIRE ALARM SYSTEM IS REQUIRED BY |
| | THE FLORIDA FIRE PREVENTION CODE. THE ACTUATION OF A |
| | DUCT SMOKE DETECTOR SHALL ACTIVATE A VISIBLE AND |
| | AUDIBLE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION. IN FACILITIES THAT ARE REQUIRED TO BE |
| | MONITORED BY A SUPERVISING STATION, DUCT SMOKE |
| | DETECTORS SHALL REPORT ONLY AS A SUPERVISORY SIGNAL, |
| | NOT AS A FIRE ALARM. |
| | |
| | EXCEPTIONS: |
| | 1.THE SUPERVISORY SIGNAL AT A CONSTANTLY ATTENDED |
| | LOCATION IS NOT REQUIRED WHERE THE DUCT SMOKE DETECTOR |
| | ACTIVATES THE BUILDING'S ALARM-INDICATING APPLIANCES. |
| | 2.IN OCCUPANCIES NOT REQUIRED TO BE EQUIPPED WITH A |
| | FIRE ALARM SYSTEM, ACTUATION OF A SMOKE DETECTOR SHALL |
| | ACTIVATE A VISIBLE AND AUDIBLE SIGNAL IN AN APPROVED |
| | LOCATION. DUCT SMOKE DETECTOR TROUBLE CONDITIONS SHALL |
| | ACTIVATE A VISIBLE OR AUDIBLE SIGNAL IN AN APPROVED |
| | LOCATION AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR |
| | TROUBLE. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |