2018-07-23 14:37:58CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL POWER WIRING NOTES STATE THAT #12 WIRE
 SHOULD BE USED FOR ALL CIRCUITS, NOTE # 2 STATES THAT
 ALL BREAKERS WILL BE 20 AMP. HOWEVER, IN EACH OF THESE
 LOCATIONS IT STATES THAT # 14 WIRE IS ACCEPTABLE.
 NUMBER 14 ROMEX IS NOT RATED FOR 20 AMPS. PROVIDE
 CORRECTION. NEC 310.15(B)(16), NEC 334.80; FBC RE
 E3705.4.4
 2. AFCI NOTE PROVIDED IS NOT CODE COMPLIANT. ALL BRANCH
 CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, 15- AND
 20-AMPERE OUTLETS INSTALLED IN KITCHENS, FAMILY ROOMS,
 DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS,
 BEDROOMS, SUN-ROOMS, RECREATIONS ROOMS, CLOSETS,
 HALLWAYS, LAUNDRY AREAS AND SIMILAR ROOMS OR AREAS
 SHALL BE AFCI PROTECTED. PROVIDE CORRECTION. NEC
 210.12; FBC RE E3902.16
 3. PLAN SHOWS A CHANDELIER OVER TUB. NO PARTS OF
 CORD-CONNECTED LUMINAIRES, CHAIN-, CABLE-, OR
 CORD-SUSPENDED LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE E4003.11
 4. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP
 CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN.
 PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D); FBC RE
 E3703.4, E3901.6
 5. GFCI PROTECTION IS REQUIRED FOR ALL RECEPTACLE
 OUTLETS IN BATHROOM. PROVIDE CORRECTION. NEC 210.8; FBC
 RE E3902.1
 6. GFCI AND AFCI PROTECTION IS IS REQUIRED FOR ALL
 RECEPTACLE OUTLETS IN LAUNDRY AREA. PROVIDE CORRECTION.
 NEC 210.8, 210.12; FBC RE E3902.9, 3902.16
 7. PLAN SHOWS A STANDARD RECESS LIGHT OVER SHOWER.
 LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE SUITABLE
 FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC 410.10(D);
 FBC RE E4003.11
 8. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 9. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  