Plan Review Notes
Plan Review Notes For Permit 18070030
Permit Number 18070030
Review Stop M
Sequence Number 4
Notes
Date Text
2019-03-21 11:18:494TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18070030
 9/19/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-102: VERIFY THE DESIGN AND OPERATION OF THE
 HAZARDOUS EXHAUST VENTILATION SYSTEM (AHU-1 AND EF-1)
 IN THE DISTILLERY SHALL BE SUCH THAT FLAMMABLE
 CONTAMINANTS ARE DILUTED IN NONCONTAMINATED AIR TO
 MAINTAIN CONCENTRATIONS IN THE EXHAUST FLOW BELOW 25
 PERCENT OF THE CONTAMINANT'S LOWER FLAMMABILITY LIMIT.
 HAS CAPTURE AND CONTAINMENT OF FLAMABLE VAPORS IN THEIR
 HEAVIEST CONCENTRATIONSAROUND THE STILLS AND TANKS BEEN
 TAKING INTO CONSIDERATION?- SECTION 502.1.1 FBC M.
  
 A) DESCRIBE THE SEQUENCE OF OPERATION FOR THE SYSTEM.
 WILL THE SYSTEM RUN CONTINUOUSLY, OR INTERMITTENTLY
 WHEN DISTILLERY OPERATIONS ARE BEING CONDUCTED? HOW
 WILL THE NEW GAS SENSORS AFFECT THE OPERATION OF THE
 VENTILATION SYSTEM. WILL THESE SENSORS BE LINKED TO THE
 SYSTEM AND ALSO TO THE FIRE ALARM?
  
 2) SUBMIT A REVISED ENERGY COMPLIANCE REPORT THAT
 INLCUDES THE NEW AC SYSTEM AND THE CHANGES TO THE
 BUILDING ENVELOPE.
  
 3) PLEASE ADJUST THE TOTAL VALUE OF THE PROPOSED
 PROJECT TO INCLUDE THE INCREASED COSTS ASSOCIATED WITH
 THE NEW EXHAUST VENTILATION SYSTEM AND SENSORS IN THE
 DISTILLERY- SECTION 109.3 FBC M.
  
 4) PLEASE NOTE THE LIST OF PROVISOS FROM THE PREVIOUS
 REVIEW.
  
 MECHANICAL PROVISOS.
 11/13/28
  
 1) PRESSURE TESTS FOR CHILLED WATER AND STEAM PIPING
 REQUIRED. REQUIRED TEST PRESSURES SHALL BE PROVIDED BY
 THE DISTILLERY SYSTEM MANUFACTURER AND THE ENGINEER OF
 RECORD.
  
 2) PROVIDE A LETTER FROM THE DISTILLERY SYSTEM
 MANUFACTURER (CORSON) CERTIFYING THE EQUIPMENT- STILLS,
 TANKS, PROCESS PIPINGS ETC.- ARE INSTALLED AND
 FUNCTIONING IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. THE LETTER SHALL BEAR
 THE APPROVAL STAMPS OF THE ENGINEER AND ARCHITECT OF
 RECORD.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE GLYCOL CHILLER AND OUTDOOR BOILER AND ASSOCIATED
 EQUIPMENT SHALL BE SUBMITTED PRIOR TO INSPECTION.
  
 6) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CHILLER, BOILER, AND THE CORSON
 DISTILLERY SYSTEM SHALL BE ONSITE AT TIME OF
 INSPECTION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  