Plan Review Notes
Plan Review Notes For Permit 18070030
Permit Number 18070030
Review Stop M
Sequence Number 3
Notes
Date Text
2018-11-13 09:49:42MECHANICAL PROVISOS.
 11/13/28
  
 1) PRESSURE TESTS FOR CHILLED WATER AND STEAM PIPING
 REQUIRED. REQUIRED TEST PRESSURES SHALL BE PROVIDED BY
 THE DISTILLERY SYSTEM MANUFACTURER AND THE ENGINEER OF
 RECORD.
  
 2) PROVIDE A LETTER FROM THE DISTILLERY SYSTEM
 MANUFACTURER (CORSON) CERTIFYING THE EQUIPMENT- STILLS,
 TANKS, PROCESS PIPINGS ETC.- ARE INSTALLED AND
 FUNCTIONING IN ACCORDANCE WITH THE MANUFACTURER'S
 GUIDELINES AND SPECIFICATIONS. THE LETTER SHALL BEAR
 THE APPROVAL STAMPS OF THE ENGINEER AND ARCHITECT OF
 RECORD.
  
 3) SITE SPECIFIC WIND LOAD ENGINEERING FOR INSTALLATION
 OF THE GLYCOL CHILLER AND OUTDOOR BOILER AND ASSOCIATED
 EQUIPMENT SHALL BE SUBMITTED PRIOR TO INSPECTION.
  
 4) A REVISED AC DUCT LAYOUT PLAN SHALL BE SUBMITTED FOR
 ALL REQUIRED ALTERATIONS MADE TO THE EXISTING SYSTEMS.
  
 5) THE RUM DISTILLERY PROCESS AND RUM STORAGE SHALL BE
 IN ACCORDANCE WITH HAZARDOUS LIQUID GUIDELINES-
 SECTIONS 307.1.2 & 414 FLORIDA BUILDING CODE SIXTH
 EDITION- 2017, AND NFPA 30-2018. PLEASE NOTE THAT A
 REVISION TO THE APPROVED MECHANICAL PLANS MAY BE
 REQUIRED BASED ON ANY REQUIRED CHANGES TO THE
 ARCHITECTURAL PLANS.
  
 6) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CHILLER, BOILER, AND THE CORSON
 DISTILLERY SYSTEM SHALL BE ONSITE AT TIME OF
 INSPECTION.