| Date |
Text |
| 2018-11-13 10:13:43 | 3RD REVIEW FBC-2017 BUILDING |
| | PERMIT #18070030 |
| | 415 SOUTHERN BLVD. |
| | TYPE OF CONSTRUCTION: II B |
| | OCCUPANCY TYPE: F-1 |
| | SPRINKLERED BLDG: NO |
| | LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF |
| | OCCUPANCY |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) PARTIALLY COMPLIED. SEE NEW COMMENTS REGARDING LIFE |
| | SAFETY PLANS. |
| | A) WHEN DETERMINING OCCUPANT LOADS PER FBC 1004.1, THE |
| | DECIMALS OF A NUMBER ARE TO BE ROUNDED UP TO THE NEXT |
| | HIGHER WHOLE NUMBER. NEW COMMENTS:THE OCCUPANT LOAD OF |
| | 3.2 FOR THE SECOND FLOOR OFFICE #202 WILL BE 4 |
| | OCCUPANTS, NOT 3. ON THE FIRST FLOOR THE 3.1 OCCUPANT |
| | LOAD OF ROOM #102 WILL BE 4 OCCUPANTS AND THE 3.27 |
| | OCCUPANTS OF ROOM #1 WILL ALSO BE 4 OCCUPANTS. |
| | B) COMPLIES. |
| | C) THE EXTERIOR EXIT STAIR IS REQUIRED BY FBC 1027.5 TO |
| | HAVE A MINIMUM FIRE SEPARATION DISTANCE OF 10 FEET |
| | MEASURED AT RIGHT ANGLES FROM THE EXTERIOR EDGE OF THE |
| | STAIRWAY. THIS STAIRWAY DOES NOT HAVE 10 FEET TO THE |
| | PROPERTY LINE OR TO THE BUILDING ON THE ADJACENT LOT. |
| | NEW COMMENTS: THE BUILDING OFFICIAL HAS DETERMINED THAT |
| | THE EXTERIOR EXIT STAIR WILL BE ALLOWED TO REMAIN AS |
| | EXISTING, AS LONG AS, THE WALL OF THE ADJACENT BUILDING |
| | IS CMU AND THE 4 X 4 WINDOW IN THE WALL IS NOT WITHIN |
| | 10 FEET OF THE EXIT STAIRS. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) ADDRESSED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) PARTIALLY COMPLIED. SPECIFY THE ITEMS AND QUANTITY |
| | OF THEM THAT WILL BE STORED ON THE SECOND FLOOR IN ROOM |
| | #204. NEW COMMENT: THE RESPONSE LETTER STATES THAT RUM |
| | WILL BE STORED WITHIN THE BUILDING ON LEVEL TWO AND/OR |
| | AS NEEDED ON LEVEL ONE. SINCE THERE WERE NO MSDS ( |
| | MATERIAL SAFETY DATA SHEETS) SUBMITTED FOR THE RUM, I |
| | WAS ABLE TO OBTAIN SOME INFORMATION ON RUM FROM THE |
| | INTERNET. THE FLASH POINT FOR 80 % ETHANOL IS 20.0 |
| | DEGREES CELCIUS (68 DEGREES F) AND THE BOILING POINT IS |
| | 78.5 DEGREES CELCIUS (173.3 DEGREES F). THIS MAKES RUM |
| | A CLASS IB FLAMABLE LIQUID. BASED ON FBC TABLE 307.1(1) |
| | A MAXIMUM OF 120 GALLONS OF RUM CAN BE STORED PER |
| | CONTROL AREA ON SITE WITHOUT BEING CONSIDERED AN H-3 |
| | OCCUPANCY. FOOTNOTE B FOR THIS TABLE STATES THAT THE |
| | AGGREGRATE QUANITY IN USE AND STORAGE SHALL NOT EXCEED |
| | THE QUANITY LISTED FOR STORAGE. FOOTNOTE C ALLOWS THE |
| | QUANTITY OF ALCOHOLIC BEVERAGES IN RETAIL AND WHOLESALE |
| | SALE OCCUPANCIES TO NOT BE LIMITED, PROVIDED THE |
| | LIQUIDS ARE PACKAGED IN INDIVIDUAL CONTAINERS NOT |
| | EXCEEDING 1.3 GALLONS. THE BUILDING OFFICIAL WILL ALLOW |
| | THE UNLIMITED STORAGE OF THE RUM IN INDIVIDUAL |
| | CONTAINERS NOT EXCEEDING 1.3 GALLONS. WHEN THE |
| | MATERIALS IN THE RUM PRODUCTION PROCESS REACH THE POINT |
| | IT BECOMES A FLAMABLE LIQUID THEN NO MORE THAN 120 |
| | GALLONS PER CONTROL AREA IS ALLOWED WITHOUT BEING |
| | CONSIDERED A HAZARDOUS OCCUPANCY (H-3). FBC 307.1 THE |
| | RUM DISTILLERY PROCESS OUTLINE THAT WAS SUBMITTED DOES |
| | NOT STATE THE AMOUNT OF RUM ( CLASS IB FLAMABLE LIQUID) |
| | THAT WILL BE IN THE PROCESS. THE PLANS SHOW A 1000 |
| | GALLON AND A 600 GALLON SPIRIT SAFE. SO IT WOULD APPEAR |
| | THAT THERE WILL BE AT LEAST 1600 GALLONS OF RUM IN THE |
| | SPIRT SAFES. THIS EXCEEDS THE 120 GALLONS ALLOWED BY |
| | FBC TABLE 307.1(1) AND WILL REQUIRE THIS AREA TO BE H-3 |
| | RATHER THAN F-1. PLEASE ADVISE AS TO HOW THIS WILL BE |
| | ADDRESSED. |
| | |
| | 8) ADDRESSED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) ADDRESSED. |
| | |
| | 11) ADDRESSED. |
| | |
| | 12) ADDRESSED. |
| | |
| | 13) ADDRESSED. |
| | |
| | 14) ADDRESSED. |
| | |
| | 15) 2017 FBC- ACCESSIBILITY - ADA |
| | 201.1 SCOPE. |
| | THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO |
| | PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL |
| | FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE |
| | SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT |
| | FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO |
| | PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO |
| | RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2), |
| | F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL |
| | NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE |
| | BUILDINGS AND FACILITIES, PLACES OF PUBLIC |
| | ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS |
| | CODE SHALL COMPLY WITH THIS CODE. |
| | THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND |
| | NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM |
| | RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED |
| | BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR |
| | FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508, |
| | F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | BUILDINGS AND FACILITIES WHERE THE ORIGINAL |
| | CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS |
| | CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW. |
| | |
| | 15-1) CLARIFY. THE LETTER FROM THE OWNER MENTIONS |
| | CUSTOMERS, WHICH WOULD BE THE PUBLIC. (IF ACCESS TO THE |
| | PRIVATE RECEPTION TASTING AREA IS ALLOWED FOR PERSONS |
| | OTHER THAN THE EMPLOYEES, THEN THE ADA REQUIREMENTS |
| | APPLY. THE FBC ACCESSIBILTY ALSO APPLIES TO PRIVATE |
| | BUILDINGS, CLUBS, ETC. IT APPEARS THAT YOUR DESIGN DOES |
| | COMPLY WITH THE EXCEPTION OF VERTICAL ACCESSIBILTY.) |
| | THE PLANS SHOW A RECEPTION/TASTING AREA THAT APPARENTLY |
| | WILL BE OPEN TO THE PUBLIC. SPECIFY WHICH AREAS WILL BE |
| | OPEN TO THE PUBLIC FOR TOURS, ETC. FBC 107.2.1 |
| | |
| | 15-2) NOT COMPLIANT. (THE RESPONSE TO THIS COMMENT |
| | STATES THAT THE SECOND FLOOR IS PRIMARILY STORAGE WITH |
| | ONE OFFICE WHICH HAS AN OCCUPANCY OF 3 PERSONS. THE |
| | PLANS STILL SHOW TWO OFFICES AND AN OCCUPANCY OF 4 |
| | PERSONS IN EACH FOR A TOTAL OF 8. THE CALCULATED |
| | OCCUPANT LOAD FOR EACH SPACE IS REQUIRED TO BE ROUNDED |
| | UP THE NEXT HIGHER WHOLE NUMBER. THE MECHANICAL ROOM |
| | 206 SHOULD NOT HAVE AN OCCUPANT LOAD. THE OCCUPANT LOAD |
| | FOR THE STORAGE AREA (3 PERSONS) DOES NOT COUNT TOWARD |
| | ACCESSIBILITY. 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS |
| | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: |
| | (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL |
| | ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE |
| | LUBRICATION AND MAINTENANCE PITS AND PLATFORMS. |
| | (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN |
| | OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS. |
| | (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE |
| | PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, |
| | INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. |
| | (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER |
| | LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR |
| | TIERED SEATING IF SECTIONS 221 AND 802 ARE MET. |
| | (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF |
| | CHAPTER 10 ARE MET. |
| | (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9. |
| | (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION |
| | 203. |
| | BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A |
| | MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA |
| | STANDARDS FOR ACCESSIBLE DESIGN. |
| | ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE |
| | APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR |
| | WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS |
| | REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL |
| | CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE |
| | THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED |
| | TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE |
| | AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS, |
| | EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM |
| | THESE REQUIREMENTS AND MUST BE ACCESSIBLE. |
| | FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN |
| | ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL |
| | ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND |
| | FACILITIES TO BE ACCESSIBLE TO PERSONS WITH |
| | DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY |
| | WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING |
| | REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA |
| | STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH |
| | AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED |
| | DOWN TO THE REQUIREMENT OF THE ADA STANDARDS. |
| | |
| | 15-3) COMPLIED. |
| | |
| | 15-4) PARTIAL COMPLIANCE. (BATHROOM MUST BE ON AN |
| | ACCESSIBLE ROUTE). NEW COMMENT: IF THE SECOND FLOOR IS |
| | REQUIRED TO HAVE VERTICAL ACCESSIBILITY, THEN THE |
| | BATHROOM ON THE SECOND LEVEL WILL HAVE TO COMPLY. |
| | WHERE TOILET FACILITIES AND BATHING FACILITIES ARE |
| | PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET |
| | FACILITIES AND BATHING FACILITIES ARE PROVIDED IN |
| | FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT |
| | TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET |
| | FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON |
| | A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN |
| | ACCESSIBLE ENTRANCE. |
| | 213.2 TOILET ROOMS AND BATHING ROOMS. |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH |
| | BATHING ROOM SHALL COMPLY WITH 603. |
| | |
| | 16) PLEASE CLARIFY THE INTENT OF THE GENERAL |
| | CONTRACTOR'S PRICING THAT WAS SUBMITTED. IS THE |
| | $90,250.00 MEANT TO BE ADDED TO THE $320,000.00 PERMIT |
| | VALUE? THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW |
| | FOR THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE |
| | CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL |
| | COST OF THE PROJECT INCLUDING, LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE |
| | WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB. |
| | 109.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |