2018-09-27 17:43:112ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. GRAB BARS SHALL BE SHOWN TO BE MEASURED TO THE TOP
 OF THE GRIPPING SURFACE FROM FINISH FLOOR. PER FBC ACC
 609.4
  
 2. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PER FBC
 ACC 604.7
  
 3. THE SINK NEXT TO THE BATHROOM APPEARS TO BE NEW IT
 DOES NOT APPEARS ON PREVIOUS PLANS IN OUR PERMIT
 RECORDS IT SHALL COMPLY WITH FBC ACC 212.2, 212.3
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED.
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 4. SHT P-102 UNDER THE FIXTURE SCHEDULE FS-1 NEEDS TO
 BE REMOVED IF THE OUTDOOR FLOOR SINK WAS DELETED , WC
 HAS THE SPECIFICATIONS FOR THE LAVATORY PLEASE COMPLY.
 PER WPB AMEND TO FBC 107.2.1
  
 5. YOU ARE MISSING THE MANUFACTURE SPECIFICATIONS FOR
 THE ETP PLEASE PROVIDE SPECS FOR THE ZURN Z1020LF AND
 THE BACFLOW FEBCO 850 ALL VALVES AND DEVICES FITTINGS
 AND PIPE CONNECT TO THE POTABLE WATER SYSTEM SHALL BE
 LEAD FREE PER FBC PL 605.2.1 PLACE NOTE ON PLAN
  
 6. BACKFLOW REQUIRED ON CW CONNECTION TO THE CHILLED
 WATER SYSTEM. PER FBC PL 608.3
  
 7. THE PREVIOUS PLANS IN OUR PERMIT RECORDS SHOWS A
 SRVICE SINK ON THE BACKSIDE OF THE LAVATORY AND A WATER
 COOLER IF THESE HAVE BEEN REMOVED AT SOME POINT IT IS
 REQUIRED TO HAVE THEM PER THE FBC PL TABLE 308.5 AND
 SHALL COMPLY WITH CURRENT CODE.
  
 8. SHT P -103 APPEARS TO HAVE BEEN REPLACED BY SHEET
 P-103A PLEASE REMOVE ALL OLD SHEETS. PER WPB AMEND TO
 FBC 107.2.1
  
 9. SEE MECHANICALLY COMMENTS FOR DISTILLING EQUIPMENT
 COMMENTS SHALL COMPLY PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  