| 2018-09-19 13:19:05 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18070030 |
| | 9/19/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) BASED ON THE NOTES ON SHEET M-102 ABOUT THE |
| | RELOCATION OF THE EXISTING AIR HANDLERS, A COMPLETE |
| | REVIEW OF THE MECHANICAL PLANS CANNOT BE ACCOMPLISHED |
| | WITHOUT THE NEW AIR HANDLER LOCATIONS SHOWN, AND A |
| | COMPLETE AC LAYOUT PLAN PROVIDED FOR BOTH THE 1ST AND |
| | 2ND FLOORS. MANY OF THE ROOMS AND SPACES ARE UNDERGOING |
| | A CHANGE OF USE FROM THEIR PREVIOUS USES, AND |
| | RECIRCULATION OF AIR FROM SOME OF THESE ROOMS AND |
| | SPACES IS NOW PROHIBITED I.E THE LAB, AND THE |
| | DISTILLERY- SEE TABLE 403.3.1.1. |
| | |
| | 2) SHEET M-102: THE EXHAUST VENTILATION CALCULATIONS |
| | ARE INCOMPLETE. CALCULATIONS FOR THE LAB, AND THE 2ND |
| | FLOOR OFFICES AND STORAGE ROOM WERE NOT PROVIDED. |
| | CONCERNING THE LAB, PLEASE PROVIDE A NARRATIVE THAT |
| | CLARIFIES THE PROCESSES THAT WILL TAKE PLACE IN THE LAB |
| | AND WHAT CHEMICALS OR MATERIALS ARE USED AND STORED IN |
| | THE LAB. PLEASE SEE SECTION 510.1 FBC M. CONCERNING THE |
| | 2ND FLOOR STORAGE ROOM, CLARIFY WHAT MATERIALS WILL BE |
| | STORED IN THE ROOM AND HOW IT WILL BRE VENTILATED. |
| | |
| | 3) M-102: REFER TO SECTION 510.9 FBC M AND INDICATE THE |
| | TYPE OF EXHAUST DUCTWORK TO BE INSTALLED FOR THE LAB |
| | AND THE BOTTLING ROOM. |
| | |
| | 4) M-102: IT APPEARS THE TERMINATIONS OF THE LAB AND |
| | BOTTLING EXHAUST ARE NOT IN COMPLIANCE WITH REQUIRED |
| | 10' CLEARANCE TO THE DOOR AND TO GRADE- SECTION 501.3.1 |
| | FBC M. |
| | |
| | 5) M-102: A SURVEY WILL BE NEEDED TO DETERMINE IF THE |
| | O/A INLET AND EXHAUST OUTLET ON THE WEST SIDE OF THE |
| | BUILDING ARE 10' CLEAR OF THE PROPERTY LINE- SECTIONS |
| | 401.4 AND 501.3.1 FBC M. |
| | |
| | 6) M-102: THE VENTILATION CALCULATION FOR THE TASTING |
| | ROOM IS NOT IN COMPLIANCE WITH TABLE 403.3.1.1. THE |
| | APPROPRIATE RATE SHALL BE BASED ON AN OCCUPANT DENSITY |
| | OF 100 PERSONS PER S.F. X 7.5 CFMS PER PERSON + 0.18 |
| | CFMS PER SQ. FT. PLEASE CORRECT. |
| | |
| | 7) THE LOUVER NOA SUBMITTAL IS MISSING PAGE 1. |
| | |
| | 8) THE SUBMIITED SPECS FOR THE RITE BOILER DO NOT |
| | PROVIDE ANY LISTING INFORMATION AS REQUIRED BY SECTION |
| | 631.1 FBC FG, OR INDICATE THE UNIT CAN BE INSTALLED ON |
| | THE EXTERIOR OF THE BUILDING. THE SPECS ARE INDICATING |
| | AN INTERIOR INSTALLATION. |
| | |
| | 9) NO ADDITIONAL INFORMATION HAS BEEN SUBMITTED AS |
| | REQUESTED FOR THE DISTILLERY TANKS, KETTLES, AND |
| | STILLS. IT IS STILL NOT CLEAR IF THE EQUIPMENT HAS BEEN |
| | TESTED IN ACCORDANCE WITH ANY LISTING AGENCY OR TESTING |
| | STANDARD- PLEASE PROVIDE ADDITIONAL INFORMATION. |
| | |
| | 10) CLARIFY IF VENTING OF THE STILLS, TANKS, AND |
| | KETTLES IS REQUIRED, AND REVISE THE PLANS ACCORDINGLY |
| | TO SHOW LOCATIONS AND VENTING DETAILS. |
| | |
| | 11) THE SUBMITTED SPECS FOR THE BOTTLING MACHINE |
| | INDICATE THE USE OF CO2 AND OXYGEN TANKS. CLARIFY IF |
| | TANKS WILL BE STORED AT THE FACILITY AND SHOW WHERE AND |
| | HOW THEY WILL BE STORED IF APPLICABLE. |
| | |
| | LISTED BELOW ARE COMMENTS FROM THE FIRST REVIEW THAT |
| | STILL EXIST- PLEASE COMPLY. |
| | |
| | 8) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION |
| | DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER |
| | ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS SHOWN ON |
| | SHEET M-100- SECTION 301.15 FBC M. |
| | |
| | 10) PLEASE PROVIDE A PLAN THAT SHOWS THE REQUIRED |
| | WORKING CLEARANCES AROUND THE STILLS, KETTLES, AS |
| | REQUIRED BY THE LISTING AGENCY OR THE MANUFACTURER, AND |
| | CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR THE |
| | INCREASED LOADS OF THE DISTILLERY EQUIPMENT- SECTION |
| | 107.2.1 WPB. |
| | |
| | 11) CLARIFY IF THE EXISTING SLAB HAS BEEN EVALUATED FOR |
| | THE INCREASED LOADS OF THE DISTILLERY TANKS, KETTLES, |
| | STILLS ETC, AND PROVIDE ANCHORING DETAILS. |
| | |
| | 12) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR |
| | THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE |
| | CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL |
| | COST OF THE PROJECT INCLUDING, LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE |
| | WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |