2018-09-28 07:04:492ND REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 GAS COMMENTS:
  
 1. PLEASE CLARIFY THE SYSTEM PRESSURE SHT. P103A UNDER
 THE GAS CALCULATIONS LIST THE PRESSURE AT 2PSIOR LESS
 IS IT 2 PSI OR IS IT LESS THAN 2 PSI. PER WPB AMEND TO
 FBC 107.2.1
  
 2. SHT. P103A THE PLAN IS SHOWING THE METER AND
 REGULATOR OUT SIDE THE NEW FENCE RIGHT IN FRONT OF THE
 PARKING STOP PLEASE SHOW ON THE THE PLAN THAT THE GAS
 RISER, METER AND REGULATOR ARE PROTECTED FROM DAMAGE
 FROM VEHICLES WITH A SUBSTANTIAL TRAFFIC BALLARD. PER
 WPB AMEND TO FBC 107.2.1
  
 3. IT WILL BE REQUIRED TO SUBMIT BEFORE PERMIT ISSUE
 TWO COPY'S OF THE MANUFACTURE SPECIFICATIONS AND
 INSTALLATION GUIDE FOR THE BOILER AND REGULATOR THE
 BOILER SPECS THAT WHERE PROVIDED DID NOT GIVE
 INFORMATION ON THE STANDARDS THAT IT MEETS OR CLEARLY
 SHOW INSTALLATION OUT DOORS. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  