| 2018-09-11 13:35:28 | PERMIT # 18070030 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | 2ND REVIEW: |
| | |
| | 1) SHEET A250: PER SECTION 8.7, ANY AREA HAVING A |
| | DEGREE OF HAZARD GREATER THAN NORMAL TO THE GENERAL |
| | OCCUPANCY OF THE BUILDING, SHALL BE SEPARATED FROM |
| | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR |
| | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS |
| | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND |
| | FIRE-RATED FOR AT LEAST 45-MINUTES. |
| | HAZARD OF CONTENTS SEPARATION IS REQUIRED BETWEEN THE |
| | INDUSTRIAL USE AREAS AND THE ASSEMBLY AREA |
| | (RECEPTION/TASTING). ADDITIONALLY, THE OFFICE USE SPACE |
| | OF THE SECOND FLOOR REQUIRES FIRE-RATED PROTECTION FROM |
| | THE MODERATE/ORDINARY HAZARD INDUSTRIAL USE AREA |
| | DIRECTLY BELOW. |
| | |
| | NFPA 101: 8.7 SPECIAL HAZARD PROTECTION. |
| | 8.7.1 GENERAL. |
| | 8.7.1.1* PROTECTION FROM ANY AREA HAVING A DEGREE OF |
| | HAZARD GREATER THAN THAT NORMAL TO THE GENERAL |
| | OCCUPANCY OF THE BUILDING OR STRUCTURE SHALL BE |
| | PROVIDED BY ONE OF THE FOLLOWING MEANS: |
| | (1) ENCLOSING THE AREA WITH A FIRE BARRIER WITHOUT |
| | WINDOWS THAT HAS A 1-HOUR FIRE RESISTANCE RATING IN |
| | ACCORDANCE WITH SECTION 8.3 |
| | (2) PROTECTING THE AREA WITH AUTOMATIC EXTINGUISHING |
| | SYSTEMS IN ACCORDANCE WITH SECTION 9.7 |
| | (3) APPLYING BOTH 8.7.1.1(1) AND (2) WHERE THE HAZARD |
| | IS SEVERE OR WHERE OTHERWISE SPECIFIED BY CHAPTERS 11 |
| | THROUGH 43 |
| | |
| | 2) INTERIOR STAIR APPEARS TO BE "OPEN", LEADING DOWN |
| | FROM AN AREA OF LOWER HAZARD TO AN AREA OF HIGHER |
| | HAZARD. AS THIS STAIR IS PART OF THE MEANS OF EGRESS, |
| | IT ALSO NEEDS TO BE REVIEWED AND PROVIDED WITH THE |
| | PROPER SEPARATION. |
| | |
| | 3) PER YOUR NARRATIVE RESPONSE, YOU INDICATE THAT THE |
| | RECEPTION/TASTING AREA WILL BE FOR "PRIVATE USE" AS A |
| | "WORK AREA". HOWEVER, YOU HAVE PROVIDED AN OCCUPANCY |
| | LOAD CALCULATION THAT EQUATES TO AN AREA THAT WILL BE |
| | USED AS AN ASSEMBLY SPACE (1:15). PLEASE CLARIFY |
| | COMMENTS. |
| | WILL THIS AREA BE IN ANY WAY ACCESSIBLE TO PERSONS |
| | OTHER THAN STAFF AND/OR DELIVERY PERSONNEL? IN OTHER |
| | WORDS, WILL THE GENERAL PUBLIC HAVE ACCESS TO IT FOR |
| | ANY REASON (I.E. PRIVATE EVENTS, SPECIAL EVENTS, |
| | PURCHASE OF GOODS, TOURS, ETC.) |
| | |
| | 4) PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | 5) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | |
| | 6) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | DELAYED EGRESS INSTALLATION. |
| | |
| | 7) ADDITIONAL PLAN REVIEW COMMENTS MAY BE GENERATED |
| | DURING PLAN RESUBMISSION. |
| | |
| | SUE ELLEN CALDERON |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |