2018-09-18 15:57:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. CORRECTED.
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. CORRECTED.
 6. CORRECTED.
 7. CORRECTED.
 8. CORRECTED.
 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND
 SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS
 MISSING. NEC 220 (PANEL A AND B DO NOT HAVE TOTALS FOR
 THE LOADS. PANEL SCHEDULE INCOMPLETE.)
 10. CORRECTED.
  
 NEW COMMENT:
  
 11. RISER DIAGRAM SHOWS FEEDERS WITH A REDUCED NEUTRAL
 TO EACH PANEL. HOWEVER, THE PANEL SCHEDULES CALL FOR
 FULL SIZE NEUTRALS. CORRECT DISCREPANCY. IF REDUCED
 NEUTRAL SIZE IS DESIRED, PROVIDE NEUTRAL DEMAND LOAD
 CALCULATION. WPB FBC 107.2.1; NEC 220.61
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  