| 2018-09-18 15:57:32 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| | SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| | COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| | HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| | COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| | |
| | 1. CORRECTED. |
| | 2. CORRECTED. |
| | 3. CORRECTED. |
| | 4. CORRECTED. |
| | 5. CORRECTED. |
| | 6. CORRECTED. |
| | 7. CORRECTED. |
| | 8. CORRECTED. |
| | 9. PROVIDE ACCURATE LOAD CALCULATION FOR EACH PANEL AND |
| | SERVICE. IT APPEARS THE LOAD FOR THE WATER HEATER IS |
| | MISSING. NEC 220 (PANEL A AND B DO NOT HAVE TOTALS FOR |
| | THE LOADS. PANEL SCHEDULE INCOMPLETE.) |
| | 10. CORRECTED. |
| | |
| | NEW COMMENT: |
| | |
| | 11. RISER DIAGRAM SHOWS FEEDERS WITH A REDUCED NEUTRAL |
| | TO EACH PANEL. HOWEVER, THE PANEL SCHEDULES CALL FOR |
| | FULL SIZE NEUTRALS. CORRECT DISCREPANCY. IF REDUCED |
| | NEUTRAL SIZE IS DESIRED, PROVIDE NEUTRAL DEMAND LOAD |
| | CALCULATION. WPB FBC 107.2.1; NEC 220.61 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |