| Date |
Text |
| 2018-09-27 09:14:43 | 2ND REVIEW FBC-2017 BUILDING |
| | PERMIT #18070030 |
| | 415 SOUTHERN BLVD. |
| | TYPE OF CONSTRUCTION: II B |
| | OCCUPANCY TYPE: F-1 |
| | SPRINKLERED BLDG: NO |
| | LEVEL OF ALTERATION: LEVEL III ALTERATION, CHANGE OF |
| | OCCUPANCY |
| | |
| | CODES IN EFFECT: |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC SIXTH EDITION (2017) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. SEE NEW COMMENTS REGARDING LIFE SAFETY |
| | PLANS. |
| | A) WHEN DETERMINING OCCUPANT LOADS PER FBC 1004.1, THE |
| | DECIMALS OF A NUMBER ARE TO BE ROUNDED UP TO THE NEXT |
| | HIGHER WHOLE NUMBER. |
| | B) SHOW THAT THE TWO EXIT ACCESS STAIRWAYS FROM THE |
| | SECOND FLOOR COMPLY WITH FBC1007.1 FOR THE REQUIRED |
| | SEPARATION DISTANCE OF ONE-HALF THE LENGTH OF THE |
| | MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR |
| | AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN |
| | THEM. |
| | C) THE EXTERIOR EXIT STAIR IS REQUIRED BY FBC 1027.5 TO |
| | HAVE A MINIMUM FIRE SEPARATION DISTANCE OF 10 FEET |
| | MEASURED AT RIGHT ANGLES FROM THE EXTERIOR EDGE OF THE |
| | STAIRWAY. THIS STAIRWAY DOES NOT HAVE 10 FEET TO THE |
| | PROPERTY LINE OR TO THE BUILDING ON THE ADJACENT LOT. |
| | |
| | 3) NOT COMPLIANT. (DESIGNER NEEDS TO REFERENCE 2017 FBC |
| | EXISTING BUILDING AND CHANGE OF OCCUPANCY ON THE |
| | PLANS.) IN ORDER TO PROVIDE A COMPLETE REVIEW, THE |
| | ARCHITECT SHALL INDICATE THE CLASSIFICATION OF WORK AS |
| | OUTLINED IN CHAPTER 5 FBC EXISTING BUILDING. THIS |
| | APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN |
| | SECTION 202 FBC EX. PLEASE SEE SECTION 506 AND CHAPTER |
| | 10 FOR ALL REQUIREMENTS. |
| | |
| | 4) NOT COMPLIANT. (DESIGNER NEEDS TO SPECIFY ON THE |
| | PLANS THAT THIS BUILDING IS A NONSEPARATED MIXED USE |
| | OCCUPANCY, F-1, B AND S-1.) SEE FBC 508.3 THE BUILDING |
| | IS FUNCTIONING AS A MULTI-USE OCCUPANCY. INDICATE IF |
| | THE BUILDING IS DESIGNED FOR MIXED USE (NON-SEPARATED) |
| | OR SEPARATED USE PER SECTION 6.1.14.3 OF NFPA 101 |
| | FLORIDA EDITION 2015. FOR NON-SEPARATED MIXED USE |
| | OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE SAFETY |
| | REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO THE |
| | BUILDING. |
| | |
| | 5) ADDRESSED. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) SEE FIRE COMMENTS. NEW COMMENT: SPECIFY THE ITEMS |
| | AND QUANTITY OF THEM THAT WILL BE STORED ON THE SECOND |
| | FLOOR IN ROOM #204. SPECIFY THE REQUIRED UNIFORMLY |
| | DISTRIBUTED LIVE LOAD FOR THIS STORAGE AREA AND THE |
| | EXISTING FLOOR LIVE LOAD FOR THIS AREA. FBC 1607.1 |
| | |
| | 8) ADDRESSED. |
| | |
| | 9) PROVIDE WIND LOAD ENGINEERING AND INSTALLATION |
| | DETAILS FOR THE CHILLER, BOILER, PUMPS, AND ALL OTHER |
| | ASSOCIATED EXTERIOR EQUIPMENT AND SUPPORTS. 2017 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | |
| | 2. RISK CATEGORY. |
| | |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 10) ADDRESSED. |
| | |
| | 11) ADDRESSED. |
| | |
| | 12) ADDRESSED. |
| | |
| | 13) ADDRESSED. |
| | |
| | 14) ADDRESSED. |
| | |
| | 15) 2017 FBC- ACCESSIBILITY - ADA |
| | 201.1 SCOPE. |
| | THIS CODE ESTABLISHES STANDARDS FOR ACCESSIBILITY TO |
| | PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL |
| | FACILITIES BY INDIVIDUALS WITH DISABILITIES. THIS CODE |
| | SHALL ALSO APPLY: TO STATE AND LOCAL GOVERNMENT |
| | FACILITIES PURSUANT TO SECTION 553.503, F.S.; TO |
| | PRIVATE CLUBS PURSUANT TO SECTION 553.505, F.S.; AND TO |
| | RESIDENTIAL BUILDINGS PURSUANT TO SECTION 553.504(2), |
| | F.S., AND THE ADA STANDARDS FOR ACCESSIBLE DESIGN. ALL |
| | NEW OR ALTERED PUBLIC BUILDINGS AND FACILITIES, PRIVATE |
| | BUILDINGS AND FACILITIES, PLACES OF PUBLIC |
| | ACCOMMODATION AND COMMERCIAL FACILITIES SUBJECT TO THIS |
| | CODE SHALL COMPLY WITH THIS CODE. |
| | THIS CODE APPLIES TO: ALL AREAS OF NEWLY DESIGNED AND |
| | NEWLY CONSTRUCTED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | PORTIONS OF ALTERED BUILDINGS AND FACILITIES AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | A BUILDING OR FACILITY THAT IS BEING CONVERTED FROM |
| | RESIDENTIAL TO NONRESIDENTIAL OR MIXED USE AS DEFINED |
| | BY THE FLORIDA BUILDING CODE WHERE SUCH BUILDING OR |
| | FACILITY MUST, AT A MINIMUM, COMPLY WITH S. 553.508, |
| | F.S., AND THE REQUIREMENTS FOR ALTERATIONS AS |
| | DETERMINED BY THE ADA STANDARDS FOR ACCESSIBLE DESIGN; |
| | BUILDINGS AND FACILITIES WHERE THE ORIGINAL |
| | CONSTRUCTION OR ANY FORMER ALTERATION OR RENOVATION WAS |
| | CARRIED OUT IN VIOLATION OF APPLICABLE PERMITTING LAW. |
| | |
| | 15-1) CLARIFY. (IF ACCESS TO THE PRIVATE RECEPTION |
| | TASTING AREA IS ALLOWED FOR PERSONS OTHER THAN THE |
| | EMPLOYEES, THEN THE ADA REQUIREMENTS APPLY. THE FBC |
| | ACCESSIBILTY ALSO APPLIES TO PRIVATE BUILDINGS, CLUBS, |
| | ETC. IT APPEARS THAT YOUR DESIGN DOES COMPLY WITH THE |
| | EXCEPTION OF VERTICAL ACCESSIBILTY.) THE PLANS SHOW A |
| | RECEPTION/TASTING AREA THAT APPARENTLY WILL BE OPEN TO |
| | THE PUBLIC. SPECIFY WHICH AREAS WILL BE OPEN TO THE |
| | PUBLIC FOR TOURS, ETC. FBC 107.2.1 |
| | |
| | 15-2) NOT COMPLIANT. ( THE RESPONSE TO THIS COMMENT |
| | STATES THAT THE SECOND FLOOR IS PRIMARILY STORAGE WITH |
| | ONE OFFICE WHICH HAS AN OCCUPANCY OF 3 PERSONS. THE |
| | PLANS SHOW TWO OFFICES AND AN OCCUPANCY OF 4 PERSONS IN |
| | EACH FOR A TOTAL OF 8. THE CALCULATED OCCUPANT LOAD FOR |
| | EACH SPACE IS REQUIRED TO BE ROUNDED UP THE NEXT HIGHER |
| | WHOLE NUMBER. THE MECHANICAL ROOM 206 SHOULD NOT HAVE |
| | AN OCCUPANT LOAD.) THE OCCUPANT LOAD FOR THE STORAGE |
| | AREA (3 PERSONS) DOES NOT COUNT TOWARD ACCESSIBILITY. ) |
| | 201.1.1 VERTICAL ACCESSIBILITY. SECTIONS |
| | 553.501-553.513, F.S., AND THE ADA STANDARDS FOR |
| | ACCESSIBLE DESIGN DO NOT RELIEVE THE OWNER OF ANY |
| | BUILDING, STRUCTURE OR FACILITY GOVERNED BY THOSE |
| | SECTIONS FROM THE DUTY TO PROVIDE VERTICAL |
| | ACCESSIBILITY TO ALL LEVELS ABOVE AND BELOW THE |
| | OCCUPIABLE GRADE LEVEL REGARDLESS OF WHETHER THE |
| | STANDARDS REQUIRE AN ELEVATOR TO BE INSTALLED IN SUCH |
| | BUILDING, STRUCTURE OR FACILITY, EXCEPT FOR: |
| | (1)ELEVATOR PITS, ELEVATOR PENTHOUSES, MECHANICAL |
| | ROOMS, PIPING OR EQUIPMENT CATWALKS AND AUTOMOBILE |
| | LUBRICATION AND MAINTENANCE PITS AND PLATFORMS. |
| | (2)UNOCCUPIABLE SPACES, SUCH AS ROOMS, ENCLOSED SPACES |
| | AND STORAGE SPACES THAT ARE NOT DESIGNED FOR HUMAN |
| | OCCUPANCY, FOR PUBLIC ACCOMMODATIONS OR FOR WORK AREAS. |
| | (3)OCCUPIABLE SPACES AND ROOMS THAT ARE NOT OPEN TO THE |
| | PUBLIC AND THAT HOUSE NO MORE THAN FIVE PERSONS, |
| | INCLUDING, BUT NOT LIMITED TO EQUIPMENT CONTROL ROOMS |
| | AND PROJECTION BOOTHS. |
| | (4)THEATERS, CONCERT HALLS, AND STADIUMS, OR OTHER |
| | LARGE ASSEMBLY AREAS THAT HAVE STADIUM-STYLE SEATING OR |
| | TIERED SEATING IF SECTIONS 221 AND 802 ARE MET. |
| | (5)ALL PLAY AND RECREATION AREAS IF THE REQUIREMENTS OF |
| | CHAPTER 10 ARE MET. |
| | (6)ALL EMPLOYEE AREAS AS EXEMPTED BY 203.9. |
| | (7)FACILITIES, SITES AND SPACES EXEMPTED BY SECTION |
| | 203. |
| | BUILDINGS, STRUCTURES AND FACILITIES MUST, AT A |
| | MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADA |
| | STANDARDS FOR ACCESSIBLE DESIGN. |
| | ADVISORY 201.1 SCOPE. THESE REQUIREMENTS ARE TO BE |
| | APPLIED TO ALL AREAS OF A FACILITY UNLESS EXEMPTED, OR |
| | WHERE SCOPING LIMITS THE NUMBER OF MULTIPLE ELEMENTS |
| | REQUIRED TO BE ACCESSIBLE. FOR EXAMPLE, NOT ALL MEDICAL |
| | CARE PATIENT ROOMS ARE REQUIRED TO BE ACCESSIBLE; THOSE |
| | THAT ARE NOT REQUIRED TO BE ACCESSIBLE ARE NOT REQUIRED |
| | TO COMPLY WITH THESE REQUIREMENTS. HOWEVER, COMMON USE |
| | AND PUBLIC USE SPACES SUCH AS RECOVERY ROOMS, |
| | EXAMINATION ROOMS, AND CAFETERIAS ARE NOT EXEMPT FROM |
| | THESE REQUIREMENTS AND MUST BE ACCESSIBLE. |
| | FLORIDA VERTICAL ACCESSIBILITY REQUIRES ALL LEVELS IN |
| | ALL NEW BUILDINGS, STRUCTURES AND FACILITIES AND ALL |
| | ALTERED AREAS OF EXISTING BUILDINGS, STRUCTURES AND |
| | FACILITIES TO BE ACCESSIBLE TO PERSONS WITH |
| | DISABILITIES. ALL NEW AND ALTERED AREAS MUST COMPLY |
| | WITH THE ADA STANDARDS FOR ACCESSIBLE DESIGN INCLUDING |
| | REQUIREMENTS FOR ACCESSIBLE ROUTES. WHERE THE ADA |
| | STANDARDS DO NOT REQUIRE AN ACCESSIBLE ROUTE TO EACH |
| | AND EVERY LEVEL, THE FLORIDA REQUIREMENT MAY BE WAIVED |
| | DOWN TO THE REQUIREMENT OF THE ADA STANDARDS. |
| | |
| | 15-3) NOT RESOLVED. PROVIDE AN ACCESSIBLE ROUTE TO AND |
| | THROUGH THE PUBLIC AREAS. FBC-A 206.1 GENERAL. |
| | ACCESSIBLE ROUTES SHALL BE PROVIDED IN ACCORDANCE WITH |
| | 206 AND SHALL COMPLY WITH CHAPTER 4. |
| | |
| | 15-4) PARTICAL COMPLIANCE. ( BATHROOM MUST BE ON AN |
| | ACCESSIBLE ROUTE.) PROVIDE AN ACCESSIBLE BATHROOM. |
| | FBC-A 213 TOILET FACILITIES AND BATHING FACILITIES |
| | 213.1 GENERAL. |
| | WHERE TOILET FACILITIES AND BATHING FACILITIES ARE |
| | PROVIDED, THEY SHALL COMPLY WITH 213. WHERE TOILET |
| | FACILITIES AND BATHING FACILITIES ARE PROVIDED IN |
| | FACILITIES PERMITTED BY 206.2.3 EXCEPTIONS 1 AND 2 NOT |
| | TO CONNECT STORIES BY AN ACCESSIBLE ROUTE, TOILET |
| | FACILITIES AND BATHING FACILITIES SHALL BE PROVIDED ON |
| | A STORY CONNECTED BY AN ACCESSIBLE ROUTE TO AN |
| | ACCESSIBLE ENTRANCE. |
| | 213.2 TOILET ROOMS AND BATHING ROOMS. |
| | WHERE TOILET ROOMS ARE PROVIDED, EACH TOILET ROOM SHALL |
| | COMPLY WITH 603. WHERE BATHING ROOMS ARE PROVIDED, EACH |
| | BATHING ROOM SHALL COMPLY WITH 603. |
| | |
| | 16) THE $320,000.00 PERMIT VALUE APPEARS TO BE LOW FOR |
| | THE SCOPE OF THE PROPOSED PROJECT. PLEASE PROVIDE |
| | CONTRACTS, INVOICES, ESTIMATES ETC. THAT SHOW THE TOTAL |
| | COST OF THE PROJECT INCLUDING, LABOR, MATERIALS, |
| | EQUIPMENT, APPLIANCES, FIXTURES, DESIGN FEES, SITE |
| | WORK, OVERHEAD AND PROFIT- SECTION 109.3 WPB. |
| | 109.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR THE |
| | MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, RACK |
| | STORAGE, EXHAUST HOODS, ANSUL SYSTEMS OR ALTERNATIVE |
| | AUTOMATIC FIRE-EXTINGUISHING SYSTEMS, WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, SCREEN ENCLOSURES, CANOPY, FENCE, |
| | LANDSCAPE, IRRIGATION, AUGER CAST PILE AND OR |
| | FOUNDATION OR STRUCTURE ONLY PERMIT WILL BE SEPARATE |
| | REVIEWS AND ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE PROVIDE AN ITEMIZED LIST AND SUBTRACT THESE LINE |
| | ITEMS AND THEIR VALUE FROM THE OVERALL BUILDING VALUE |
| | STATED ON THE PERMIT APPLICATION FOR THIS PROJECT. THE |
| | REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF THE |
| | BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DEPARTMENT DOES NOT WANT TO COLLECT TWICE FOR |
| | THE VALUE OF THESE SUB-PERMITS NOT COVERED UNDER THE |
| | PRIME OR MASTER PERMIT. |
| | |
| | 17) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |