| 2018-08-09 08:37:36 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE INDICATE THE TYPE OF OCCUPANCY ON THE PLAN. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. PLEASE INDICATE ON THE PLAN THE LEVEL OF ALTERATION |
| | IT APPEARS TO BE A CHANGE OF OCCUPANCY FROOM A BUSINESS |
| | TO AN F-1 AND THERE FOR SHALL COMPLY WITH FBC EX CH 10 |
| | |
| | 3. LIST OCCUPANT LOAD ON PLAN. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. THIS ALTERATION SHALL COMPLY WITH FBC ACC 202.4 |
| | PLEASE PROVIDE A COST BREAK DOWN TO SHOW COMPLIANCE. |
| | PER FBC ACC 202.4.1, 202.4.2 |
| | |
| | 5. PROVIDE MANUFACTURE SPECIFICATIONS FOR ETP, WATER |
| | SOFTENER AND THE CONDENSATE RETURN WATER SYSTEM. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. PLEASE PROVIDE MANUFACTURE SIZING CALCULATIONS FROM |
| | SCHIER FOR THE GREASE INTERCEPTOR. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 7. THE FLOOR DRAIN NEXT TO THE BOILER IS NOT VENTED. |
| | PER FBC PL 901.2.1 |
| | |
| | 8. THE FLOOR DRAIN NEXT TO THE BOILER APPEARS TO BE ON |
| | THE EXTERIOR OF THE BUILDING THE SANITARY SHALL NOT |
| | RECEIVE RAIN WATER HOW WILL THIS FLOOR DRAINBE |
| | PROTECTED FROM RECEIVING RAIN WATER. PER CITY OF WEST |
| | PALM BEACH CODE O ORDINANCE SEC. 90-126.(5) |
| | |
| | 9. SHT PP-101 THE BOILER IS MISSING THE WATER |
| | CONNECTION ON THE FLOOR PLAN AND THE WATER ISOMETRIC |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. A BACK FLOW IS REQUIRED ON THE EPT AND THE |
| | CONDENSATE RETURN FEED WATER SYSTEM. PER FBC PL 608.3 |
| | |
| | 11. SHT P-104 DETAIL B SHOWS A SHELF BRACKET WITH A |
| | RATING OF 150LBS A 45GAL WATER HEATER WEIGHS OVER |
| | 400LBS WHEN IT IS FULL PLEASE PROVIDE A PLATFORM SYSTEM |
| | THAT EXCEEDS THIS WEIGHT. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. SHT. P-104 DETAIL G AND M SHOW A SINGLE TRAP PRIMER |
| | VALVE THE WATER ISOMETRIC SHOWS A LARGE MULTI PORT |
| | ELECTRONIC TRAP PRIMER VALVE PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |